5.4.2 Buffer tank - Temperatures
System menu
Buffer tank
Heating circuit release from following buffer tank temperature
30°C
Temperature value which must be reached to release the heating circuit pumps in the top part of the buffer
tank.
NOTICE! This parameter applies for all available heating circuits!
Buffer tank fully loaded if temperature difference between boiler and bottom buffer tank
10°C
From this difference between the boiler temperature setpoint that has been set and the current temperature in
the lower part of the buffer tank, buffer tank loading is stopped.
5.4.3 Buffer tank - Times
System menu
Buffer tank
⇨ See "Setting times" [page 13]
Menu overview and parameters
5
Buffer tank
Operating Instructions RBG 3200 Touch | B0780115_en
27