SIRe Advanced Fan Heater Water
23
GB
Start-up wizard
Fan step 1-5
Heating step off-1
Checking system...
Set language
English
Start-up wizard
1
Start-up wizard
Set temp. unit
°C
°
F
2
Start-up wizard
Set date
2011
-05-28
YYYY-MM-DD
3
Start-up wizard
Set time
14
:07
24h format
4
Start-up wizard
Function test
Start test
Skip test
5
Start-up wizard
Function test
Test completed
Restart test
6
Start-up wizard
Start-up finished
Proceed
Restart wizard
10
Start-up wizard
External filter guard
OFF
ON
8
Start-up wizard
Mixing cabinet on/off
OFF
ON
9
Start-up wizard
Eco / Comfort
Comfort mode
Eco mode
7
Start up
System supplied with power. At the first start
up, the start-up wizard is run and the basic
settings are made. Fan and heating steps
are tested through the test program. Then a
status window is displayed.
At the first start up alarm and error codes
can occur, these will usually be reset without
actions.
Unit with mixing cabinet
When a mixing cabinet is used the supplied
Return temp. sensor SIReWTA must be
installed. SIReWTA is a clamp-on sensor
which is installed on the return water pipe as
close to the coil as possible. The sensor must
be insulated so it is not influenced by the
ambient temperature.
In order for the Return temp. Sensor to
detect the correct temperature in the return
circuit when the valve actuator is closed, a
circulation pump must be installed in the
secondary circuit.
Damper motor PSM01 must be installed on
the throttle spindle to the mixing cabinet.
Electrical connection between the damper
motor and PC board HUB SIReA1X and
transformer ST23024 (see the wiring diagram
at the end of the manual).
Start up
Select mixing cabinet On in the start-up
wizard.
Jumper settings
Actuator SDM24 (included in the valve kit) is
adjustable, this is done with jumpers. These
are located under the hatch of the actuator.
To SDM24 to work with SIRe the setting
should be as follows:
1
2
3
4
5
6
1-4, 6:Jumper in place
5:Jumper not in place
Jumper 4 and 6 are not in use.
Start-up wizard
Screen function test