Operating modes

Operating modes (without mixing cabinet)

Control is based on the four operating modes:

• Auto
• Thermostat / Manual fan
• Thermostat / Automatic fan
• Manual

 

Auto

When the set point value is undercut by 0.5 K 
the fan starts at speed 1 and the valve motor 
starts to open stepless. If a fully open valve is 
not sufficient to maintain the temperature, 
the fan control increases to a max of step 4. 
The difference between the setpoint value and 
the room temperature for the fan to increase 
one step is set under Heating step diff., see 
Installer menu > Settings heating > Heating 
step diff.
When Auto is active the fan speed and heating 
cannot be changed in the status window.   
 

Thermostat / Manual fan 

The thermostat just controls the heating and 
the fan runs continually. The fan speed is set 
manually. The fan symbol is marked in the 
status window, select desired speed with the 
rotary dial and confirm. 
 

Thermostat / Automatic fan  

The thermostat controls both the heating and 
the fan. The fan speed is set manually in the 
status window. [Installer menu > Settings fan 
> Fan mode.]
 [Installer menu > Settings fan > Fan mode.]
 

Manual 

The fan speed and heating is set manually in 
the status window. Heating can be set to 3 
steps (33%, 66% and 100%). Heating is blocked 
by the outdoor temperature, see: [Installer 
menu > Settings heating > Outdoor temp. 
limit]

 

Operating modes (with mixing cabinet)

The control is based on two operating modes: 
 
Thermostat / Manual fan
Manual
 

Thermostat / Manual fan 

The thermostat just controls the heating and 
the fan runs continually. The fan speed is set 
manually. The fan symbol is marked in the 
status window, select desired speed with the 
rotary dial and confirm. 
 

Day mode

In day mode or if no week program is 
activated, the fan runs continuously at the 
fixed fan control and the damper is open 
according to the setting under Day damper 
pos.. The heating is controlled via the room 
temperature. If the inflow temperature drops 
below the set minimum value, heat connects 
even if it is sufficiently warm in the premises.
 

Night mode

Night time (when the week program is 
activated or via external signal for night 
reduction) the damper is fully closed or 
open according to the setting under Night 
damper pos. Heating  is controlled by the 
room temperature and the fan is running 
continously. 
 

Manual 

The fan speed and heating is set manually in 
the status window. Heating can be set to 3 
steps (33%, 66% and 100%). Heating is blocked 
by the outdoor temperature, see: [Installer 
menu > Settings heating > Outdoor temp. 
limit]

 When the mixing cabinet is activated 

the Return temp. sensor SIReWTA is also 
activated. If this sensor is not installed an 
alarm is indicated. The return temperature 
sensor must be installed to reset the alarm 
[Settings heating> Return water temp.

 

Summary of Contents for sirefa

Page 1: ...SIRe Advanced Fan Heater Water With quick guide SIReFA SIReFAWM For wiring diagram please see last pages Original instructions 102 IT 82 ES 122 NL 142 NO 182 RU 162 PL 22 GB 2 SE 42 DE 62 FR...

Page 2: ...for water control and outdoor sensor SIReOTX is connected on PC Board HUB SIReA1X Transformer for voltage supply of the valve actuator is connected with quick terminal block on PC Board Base SIReB1 X...

Page 3: ...t with mixing cabinet When a mixing cabinet is used the supplied Return temp sensor SIReWTA must be installed SIReWTA is a clamp on sensor which is installed on the return water pipe as close to the c...

Page 4: ...modes without mixing cabinet 29 Operating modes with mixing cabinet 29 Control unit SIReUA1 Overview 30 Statuswindow 30 Main menu Current settings 31 Temperature settings 31 Fan control 31 System on o...

Page 5: ...ard HUB Advanced 202x139x50 SIReOTX Outdoor temperature sensor 70x33x23 SIReCC603 Modular cable RJ12 6 6 3 SIReCC605 Modular cable RJ12 6 6 5 Integrated in fan heater Wall unit cover SIReFA without mi...

Page 6: ...9x50 SIReOTX Outdoor temperature sensor 70x33x23 SMM24 Damper motor 24V 241x116x88 SIReWTA Clamp on sensor RJ11 4 4 3 SIReCC603 Modular cable RJ12 6 6 3 SIReCC605 Modular cable RJ12 6 6 5 SIREFAWM wit...

Page 7: ...7 87 510 17 Modular cable RJ11 4 4 3 SIReCC405 673 09 28 87 510 18 Modular cable RJ11 4 4 5 SIReCC410 673 09 29 87 510 19 Modular cable RJ11 4 4 10 SIReCC415 673 09 30 87 510 20 Modular cable RJ11 4 4...

Page 8: ...and modulating DN15 VMOP15NF 673 09 52 Pressure independent and modulating DN15 VMOP20 673 09 53 Pressure independent and modulating DN20 VMOP25 673 09 54 Pressure independent and modulating DN25 VMT1...

Page 9: ...or temperature see Installer menu Settings heating Outdoor temp limit Operating modes with mixing cabinet The control is based on two operating modes Thermostat Manual fan Manual Thermostat Manual fan...

Page 10: ...night mode or Off when week program is used This also displays whether the control is set to auto mode or manual mode Forward arrow Confirm selection and proceed Rotary dial Scroll between alternative...

Page 11: ...sired room temperatures to apply for day respectively night mode when the door is closed room temperature night is used for week program night reduction Factory setting Room temp day 20 C 5 35 C Room...

Page 12: ...he Installer menu code 1932 is entered Select the digits using the rotary dial and confirm using the forward arrow Installer status screen Check the settings The installer status screen consists of th...

Page 13: ...an OFF Installer menu Fan settings Week program is activated by selecting On under Week program on off In On mode a sun moon or Off in the Status window appears to indicate day night respectively Off...

Page 14: ...adually to full heating 3 Slows down the fan Max outlet temp limit 32 C Heating step diff When the temperature falls below the set point value the fan speed increases the high speed limit is position...

Page 15: ...On under Filter timer on off Factory setting Filter timer on off Off On External filter guard If an external filter guard e g a pressure switch is used it is activated under External filter guard sele...

Page 16: ...staller menu Mixing cabinet Installer menu Mixing cabinet Day damper pos 100 Installer menu Mixing cabinet Installer menu Mixing cabinet Night damper pos Min outlet temp Day damper pos 0 Day damper po...

Page 17: ...test Skip test Installer menu General settings Function test Test completed Restart test Installer menu General settings Heating step off 1 Fan step 1 5 General settings Possibility of making general...

Page 18: ...an overheating alarm A2 At internal temperatures of 100 C the fan runs at maximum speed If the unit cools heating is automatically reengaged The alarm remains in the control unit s display If the uni...

Page 19: ...low temperature and internal temperature sensor A3 Frost protection alarm The temperature in the unit has fallen below the alarm limit for frost protection Only applies to units with internal unit tem...

Page 20: ...activated see the Settings heating section E8 Internal sensor faults Fault on or missing internal sensor in the unit Check connection of the sensor If there is no sensor contact Frico for support E10...

Page 21: ...5 mA Signal from SIRe indicates fan control corresponds to 0 100 fan control Always active Heating indication 0 10V DC OUT max 5 mA Signal from SIRe indicates connected heating step Always active Cont...

Page 22: ...ALARM OUT BMS potential free contact max 3A 230V 7 8 9 10 1112 15 161718 19 20 COM 1 COM 2 BUS not in use ROOM SIReA1X C2 X5 C1 X4 ROOM X3 Pot Unit ID SIReB1 N L PE BMS INDICATION OUT potential free...

Page 23: ...10V DC IN EXTERNAL ON OFF 5 30V AC DC ALARM OUT BMS potential free contact max 3A 230V 7 8 9 10 1112 15 161718 19 20 COM 1 COM 2 BUS not in use ROOM SIReA1X C2 X5 C1 X4 ROOM X3 Pot Unit ID SIReB1 N L...

Page 24: ...5 C1 X4 ROOM X3 Pot Unit ID SIReB1 N L PE SIReWTA optional SIReUA1 SIReSDM24 SIReSDM24 ST23024 ACTUATOR SUPPLY ACTUATOR SUPPLY ACTUATOR SUPPLY EXTERNAL SETBACKTEMP on off potential free contact EXTERN...

Page 25: ...B Tel 46 31 336 86 00 Box 102 Fax 46 31 26 28 25 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se Art no E44...

Reviews: