background image

SIRe Advanced Fan Heater  Water

38

GB

Alarm and error codes  

SIRe has different alarms and error codes for 
safe and problem free operation.
If alarms or error codes have been indicated 
these must be reset in order to return to 
normal operation, for example activating the 
heating again. Fan mode is active even when, 
for example, the over heating alarm has been 
indicated.

Displaying alarm and error codes

In event of alarm or error the alarm/error 
code is shown in the status window. In event 
of alarm/error code the unit it applies to is 
displayed. 
See Table - Alarms and Table – Error codes.
 

Reset alarm

Note! Before resetting, check that the fault is 
rectified and there is nothing to prevent the 
unit from being recommissioned!

 When the fault is rectified, the alarm is 

reset by pressing the forward arrow and 
selecting Reset alarm and then confirm. 
If several units give an alarm at the same 
time, the fact that there are several alarms 
is indicated, but only one is shown in the 
display. By resetting that alarm the next 
alarm can be read. 

At the first start up alarm and error codes 

can occur, these can usually be reset without 
action.

Overheat protection

The overheat protection is designed to limit 
the temperature of the heater to a maximum 
of +90° C. If the temperature should exceed 
95°C e.g. in the event of a faulty valve or 
actuator, the fan starts to speed up to keep 
the temperature down. 
At the same time there is an overheating 
alarm A2. At internal temperatures of +100°C 
the fan runs at maximum speed.

If the unit cools, heating is automatically 

reengaged. The alarm remains in the control 
unit’s display. If the unit overheats twice 
within an hour, the fan operates until the 
alarm is reset.

 

Power failure

Note that in case of power failure the time 
settings need to be checked, if the time is not 
set correctly week program will be affected.

Frost protection function

The frost protection function is intended to 
prevent the water coil from freezing. 

 When the fan is in operation the valve 

actuator opens the valve at an internal 
temperature below +15°C regardless of 
whether there is a heating requirement. If the 
internal unit temperature continues to  drop, 
e.g. at low ambient temperatures, insufficient 
flow line temperatures, low flow or fault valve 
function, the frost protection alarm A3 will be 
triggered when the internal unit temperature 
drops +5°C. The fan then also stops and when 
the mixing cabinet is used the dampers is also 
closed.

 With return temp. sensor SIReWTA 

connected an advanced alarm function 
occurs. At return temperatures less than 
+15°C the actuator will open regardless of 
the heat demand. Alarm is triggered at return 
tempe7°C and the fan also stops.

When the fan is not running there is a heat 

retention function that opens the valve when 
the water’s return temperature falls below 
+25°C regardless of heat demand.

 Note! In event of repeated alarms, 

overheating alarms and frost protection 
alarms, carry out a thorough check and if 
the fault cause cannot be found contact 
authorised installer or Frico. 

 

Summary of Contents for sirefa

Page 1: ...SIRe Advanced Fan Heater Water With quick guide SIReFA SIReFAWM For wiring diagram please see last pages Original instructions 102 IT 82 ES 122 NL 142 NO 182 RU 162 PL 22 GB 2 SE 42 DE 62 FR...

Page 2: ...for water control and outdoor sensor SIReOTX is connected on PC Board HUB SIReA1X Transformer for voltage supply of the valve actuator is connected with quick terminal block on PC Board Base SIReB1 X...

Page 3: ...t with mixing cabinet When a mixing cabinet is used the supplied Return temp sensor SIReWTA must be installed SIReWTA is a clamp on sensor which is installed on the return water pipe as close to the c...

Page 4: ...modes without mixing cabinet 29 Operating modes with mixing cabinet 29 Control unit SIReUA1 Overview 30 Statuswindow 30 Main menu Current settings 31 Temperature settings 31 Fan control 31 System on o...

Page 5: ...ard HUB Advanced 202x139x50 SIReOTX Outdoor temperature sensor 70x33x23 SIReCC603 Modular cable RJ12 6 6 3 SIReCC605 Modular cable RJ12 6 6 5 Integrated in fan heater Wall unit cover SIReFA without mi...

Page 6: ...9x50 SIReOTX Outdoor temperature sensor 70x33x23 SMM24 Damper motor 24V 241x116x88 SIReWTA Clamp on sensor RJ11 4 4 3 SIReCC603 Modular cable RJ12 6 6 3 SIReCC605 Modular cable RJ12 6 6 5 SIREFAWM wit...

Page 7: ...7 87 510 17 Modular cable RJ11 4 4 3 SIReCC405 673 09 28 87 510 18 Modular cable RJ11 4 4 5 SIReCC410 673 09 29 87 510 19 Modular cable RJ11 4 4 10 SIReCC415 673 09 30 87 510 20 Modular cable RJ11 4 4...

Page 8: ...and modulating DN15 VMOP15NF 673 09 52 Pressure independent and modulating DN15 VMOP20 673 09 53 Pressure independent and modulating DN20 VMOP25 673 09 54 Pressure independent and modulating DN25 VMT1...

Page 9: ...or temperature see Installer menu Settings heating Outdoor temp limit Operating modes with mixing cabinet The control is based on two operating modes Thermostat Manual fan Manual Thermostat Manual fan...

Page 10: ...night mode or Off when week program is used This also displays whether the control is set to auto mode or manual mode Forward arrow Confirm selection and proceed Rotary dial Scroll between alternative...

Page 11: ...sired room temperatures to apply for day respectively night mode when the door is closed room temperature night is used for week program night reduction Factory setting Room temp day 20 C 5 35 C Room...

Page 12: ...he Installer menu code 1932 is entered Select the digits using the rotary dial and confirm using the forward arrow Installer status screen Check the settings The installer status screen consists of th...

Page 13: ...an OFF Installer menu Fan settings Week program is activated by selecting On under Week program on off In On mode a sun moon or Off in the Status window appears to indicate day night respectively Off...

Page 14: ...adually to full heating 3 Slows down the fan Max outlet temp limit 32 C Heating step diff When the temperature falls below the set point value the fan speed increases the high speed limit is position...

Page 15: ...On under Filter timer on off Factory setting Filter timer on off Off On External filter guard If an external filter guard e g a pressure switch is used it is activated under External filter guard sele...

Page 16: ...staller menu Mixing cabinet Installer menu Mixing cabinet Day damper pos 100 Installer menu Mixing cabinet Installer menu Mixing cabinet Night damper pos Min outlet temp Day damper pos 0 Day damper po...

Page 17: ...test Skip test Installer menu General settings Function test Test completed Restart test Installer menu General settings Heating step off 1 Fan step 1 5 General settings Possibility of making general...

Page 18: ...an overheating alarm A2 At internal temperatures of 100 C the fan runs at maximum speed If the unit cools heating is automatically reengaged The alarm remains in the control unit s display If the uni...

Page 19: ...low temperature and internal temperature sensor A3 Frost protection alarm The temperature in the unit has fallen below the alarm limit for frost protection Only applies to units with internal unit tem...

Page 20: ...activated see the Settings heating section E8 Internal sensor faults Fault on or missing internal sensor in the unit Check connection of the sensor If there is no sensor contact Frico for support E10...

Page 21: ...5 mA Signal from SIRe indicates fan control corresponds to 0 100 fan control Always active Heating indication 0 10V DC OUT max 5 mA Signal from SIRe indicates connected heating step Always active Cont...

Page 22: ...ALARM OUT BMS potential free contact max 3A 230V 7 8 9 10 1112 15 161718 19 20 COM 1 COM 2 BUS not in use ROOM SIReA1X C2 X5 C1 X4 ROOM X3 Pot Unit ID SIReB1 N L PE BMS INDICATION OUT potential free...

Page 23: ...10V DC IN EXTERNAL ON OFF 5 30V AC DC ALARM OUT BMS potential free contact max 3A 230V 7 8 9 10 1112 15 161718 19 20 COM 1 COM 2 BUS not in use ROOM SIReA1X C2 X5 C1 X4 ROOM X3 Pot Unit ID SIReB1 N L...

Page 24: ...5 C1 X4 ROOM X3 Pot Unit ID SIReB1 N L PE SIReWTA optional SIReUA1 SIReSDM24 SIReSDM24 ST23024 ACTUATOR SUPPLY ACTUATOR SUPPLY ACTUATOR SUPPLY EXTERNAL SETBACKTEMP on off potential free contact EXTERN...

Page 25: ...B Tel 46 31 336 86 00 Box 102 Fax 46 31 26 28 25 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se Art no E44...

Reviews: