SIRe Advanced Fan Heater Water
35
GB
>Installer menu
External control
Heating settings
Filter guard settings
>Installer menu>Filter guard
settings
External filter guard
Filter timer on/off
Filter timer setting
>Installer menu>Filter guard
settings
Filter timer setting
•
1500 h
>Installer menu>Filter guard
settings
External filter guard
Filter timer on/off
Filter timer setting
>Installer menu>Heating
settings
Control range limit
•
35°C
>Installer menu>Heating
settings
Stepless heat control
Return water temp.
Control range limit
Last filter change
Filter timer setting
External filter guard
>Installer menu
>Installer menu>Filter guard
settings
External filter guard
Filter timer setting
Last filter change
>Installer menu>Filter guard
settings
Last filter change
0 h
>Installer menu>Mixing
cabinet
Day damper pos.
Mixing cabinet on/off
Min outlet temp.
>Installer menu>Mixing
cabinet
Min outlet temp.
•
15°C
External control
Filter guard settings
Mixing cabinet
>Installer menu>Mixing
cabinet
Mixing cabinet on/off
>Installer menu
Filter timer on/off
Filter alarm is activated by selecting On,
under Filter timer on/off.
Factory setting
Filter timer on/off: Off (On)
External filter guard
If an external filter guard, e.g. a pressure
switch, is used, it is activated under External
filter guard, select On.
Factory setting
External filter guard: Off (On)
Last filter change
To check the number of run time hours since
the last filter replacement, select Last filter
change. The time is reset when the filter
alarm is reset. If the time is to be reset before
the alarm has gone, switch the filter timer on
and off.
Mixing cabinet
When the mixing part is used, it is activated
under Mixing cabinet settings.
Factory setting
Mixing cabinet on/off: Off (On)
When the mixing cabinet is activated, more
options are available in the menu under
Mixing cabinet settings.
Min outlet temp.
The outlet temperature must be limited under
Min. outlet temp.
Factory setting
Min outlet temp.: 15°C (5 – 30°C)
Control range limit
The maximum room temperature that a user
can select is limited to between 5 – 35°C.
Factory setting
Control range limit temperature: 35°C (5 –
35°C)
Filter guard settings
Filter alarm alarms when the set fixed run
time has been exceeded.
Filter timer setting
Under Filter timer setting, set the desired run
time to between 50 and 9950 hours.
Factory setting
Filter timer setting: 1500 h (50 - 9950 h)