VYPER
™
VARIABLE SPEED DRIVE
OPERATION
100-210 IOM (
JUL
09)
Page 41
PROGRAMMING PID SETUP
Step 1:
(See Figure 40) The PID Setup Screen requires
programming so that the Quantum
™
LX panel will control
the cooling system for the Vyper
™
Drive. Advance to the
PID Setpoints Screen by pressing the [
MENU
] key and then
selecting “
Setpoints
”, “
PID Setup
”, and “
Page 2
” .
Step 2:
(See Figure 40) Use the cursor arrow and [
Tab
] keys
to navigate between setpoints. With the keypad, program the
parameters listed in Table 13 under “PID #5” on the PID Setup
Screen. Press the [
Enter
] key to accept each setpoint.
Step 3:
Press the [
Submit
] key to accept the changes to PID
Channel 5 and return to the operating status screen.
Figure 40 - PID Setup Screen (Page 2)
PID Parameter
Value
Name
Drive Cooling
Control
Running
Action
Forward
Control Point
Vyper
™
Coolant*
Device Source
Analog Board 2
Device Channel
1
Setpoint
100°F
Dead Band
0.0°F
Proportional Band
20°F
Integration Time
30
High Limit
100%
Low Limit
0%
When Running OFF Value
0%
Table 13 – PID Channel #5 Setpoints