CONFIGURING COMPRESSOR OPERATION
Step 1:
(See Figure 38) Verify the Vyper
™
Drive is set to be
controlled by the Quantum
™ `
LX panel. Press the [
Menu
]
key and select “
Configuration
” at the pull-down. Select
“
Compressor
” and then “
Configuration
” once again from
the menu pull-down. This accesses the compressor Con-
figuration Screen.
Step 2:
(See Figure 38) Program the date, time, and select
the capacity regulations and miscellaneous setpoints, as
necessary using the cursor arrow and [
Tab
] keys to move
around the screen to each setpoint. Press the [
Enter
] key to
accept the new value for each setpoint.
Step 3:
(See Figure 38) At the “Drive” field under the Package
heading, verify the compressor with Vyper
™
is programmed
(See Callout 1). This allows control of the Vyper
™
Drive as
well as enables Vyper
™
-specific screens to be displayed on
the control panel.
Step 4:
Press the [
Submit
] key to accept changes and return
to the Operating Status Screen.