FR500F Series Special Purpose Inverter
- 33 -
F13.21
Holding time of PID
initial value
0.0
~
6000.0s
0.0s
×
F13.22
PID output frequency
upper limit
PID output frequency lower limit
~
100.0%
(
100.0% corresponds to
maximum frequency
)
100.0%
×
F13.23
PID output frequency
lower limit
–100.0%
~
PID output frequency
lower limit
0.0%
×
F13.24
Low limit of
PID feedback loss
0.1
~
100.0%
0.0%: Not judging feedback loss
0.0%
×
F13.25
Detection time for low limit
of
PID feedback loss
0.0
~
30.0s
1.0s
×
F13.26
PID operation at stop
Unit’s place: operation mode
0: No PID operation at stop
1: PID operation at stop
0000
×
Ten’s place: PID output limit
0: Not limit
1: limit
Hundred’s place: PID UP/DOWN
given
0: Zero-clearing when power off
1: Remain when power off
Thousand’s place: PID feedback
loss detection method
0: No detection when stop
1: Do detection when stop
Ten thousand’s place: Action when
PID feedback loss
0: Report Err
1: Ramp to stop
F13.27
PID UP/DOWN speed
0.0
~
100.0% (0.0%invalid)
0.0%
△
F13.28
Upper limit of
PID feedback loss
0.1
~
100.0%
0.0%: Not judging feedback loss
100.0%
×
F13.29
Detection time for upper
limit of
PID feedback loss
0.0
~
30.0s
1.0s
×
F13.30
PID upper limit source
0:F13.22
1:F13.22*VP
2:F13.22*AI1
3:F13.22*AI2
4:F13.22*HI
5:F13.22*AI3
0
×
F13.31
PID lower limit source
0:F13.23
1:F13.23*VP
2:F13.23*AI1
3:F13.23*AI2
4:F13.23*HI
5:F13.23*AI3
0
×
Group F14: Swing Frequency, Fixed Length ,
Wakeup and Count
F14.00
Swing frequency setting
mode
0: Relative to the setting
frequency
0
×
1: Relative to the maximum
frequency
F14.01
Swing frequency
amplitude
0.0
~
100.0%
0.0%
△
F14.02
Jump frequency amplitude
0.0
~
50.0%
0.0%
△