FR500F Series Special Purpose Inverter
- 24 -
HI
F06.33
Set value corresponding to
minimum input of curve HI
-100.0
~
100.0%
0.0%
△
F06.34
Maximum input of curve HI
Minimum input of curve HI
~
100.00kHz
50.00kHz
△
F06.35
Set value corresponding to
maximum input of curve HI
-100.0
~
100.0%
100.0%
△
F06.36
HI terminal filtering time
0.000
~
10.000s
0.100s
△
Group F07 Analog and Pulse Output
F07.00
AO1 output function
0: No output
1: Output frequency
2: Command frequency
3: Output current
4: Output voltage
5: Output power
6: Bus voltage
7:+10V
8: keypad potentiometer
9:AI1
10:AI2
11:AI3
12:HI
13: Output torque
14: Ao communication given 1
15: Ao communication given 2
1
×
F07.01
AO2 output function
2
×
F07.02
Y2/HO output function
(when used as HO)
1
×
F07.03
AO1 offset
-100.0
~
100.0%
0.0%
△
F07.04
AO1 gain
-2.000
~
2.000
1.000
△
F07.05
AO1 filtering time
0.000
~
10.000s
0.000s
△
F07.06
AO2 offset
-100.0
~
100.0%
0.00%
△
F07.07
AO2 gain
-2.000
~
2.000
1.000
△
F07.08
AO2 filtering time
0.000
~
10.000s
0.000s
△
F07.09
HO maximum output
pulse frequency
0.01
~
100.00kHz
50.00kHz
△
F07.10
HO output filtering time
0.000
~
10.000s
0.010s
△
Group F08 Parameters of Motor 1
F08.00
Motor 1 type selection
0: Three phase asynchronous
motors
0
×
1: Reserved
2: Single phase asynchronous
motors
(
Remove capacity
)
3: Single phase asynchronous
motors
(
No need to remove
capacity
)
F08.01
Power rating of motor 1
0.1
~
1000.0kW
Model
defined
×
F08.02
Rated voltage of motor 1
60
~
660V
Model
defined
×
F08.03
Rated current of motor 1
0.1
~
1500.0A
Model
defined
×
F08.04
Rated frequency of
motor 1
20.00
~
Fmax
Model
defined
×
F08.05
Rated speed of motor 1
1
~
30000
Model
defined
×
F08.08
Stator resistance R1 of
async motor 1
0.001
~
65.535Ω
Model
defined
×