FR500F Series Special Purpose Inverter
- 20 -
key) adjustment clear
13: Multi-step frequency terminal 1
14: Multi-step frequency terminal 2
15: Multi-step frequency terminal 3
16: Multi-step frequency terminal 4
17: Accel/Decel time determinant 1
18: Accel/Decel time determinant 1
19: Accel/Decel disabled(ramp
stop not inclusive)
20: Switch to auxiliary speed
setting
21: PLC status reset
22: Simple PLC paused
23: Simple PLC paused
24: PID adjustment direction
25: PID integration paused
26: PID parameter switch
27: Swing frequency pause(output
the currentfrequency)
28: Swing frequency reset(output
the central frequency)
29: Run command switched to
keypad contro
30: Run command switched to
terminal control
31: Run command switched to
communication control
32: Count input
33: Count clear
34: Length count
35: Length clear
36: DC brake input command at
Stop
37: Speed/torque control switch
38: No reverse
39: No forward
F04.10
Filtering time of digital
input terminal
0.000
~
1.000s
0.010s
△
F04.11
Delay time before terminal
DI1 is valid
0.0
~
300.0s
0.0s
△
F04.12
Delay time before terminal
DI2 is valid
0.0
~
300.0s
0.0s
△
F04.13
Terminal DI1
~
DI5
positive/negative logic
DI5
、
DI4
、
DI3
、
DI2
、
DI1
00000
×
0: Positive logic(Terminals are on
at 0V/off at 24V)
1: Negative Logic (Terminals are
off at 0V/on at 24V)
F04.14
Terminal DI6
~
AI3
positive/negative logic
AI3
、
AI2
、
AI1
、
DI7
、
DI6
00000
×
0: Positive logic
1: Negative Logic
F04.15
FWD/REV terminal
control mode
0: Two-wire mode 1
0
×
1: Two-wire mode 2
2: Three-wire mode 1
3: Three-wire mode 2
F04.16
Terminal UP/DOWN
frequency adjustment
Unit's place: action when stop
001
×
0: Clear