![FRC Turbofoam TFC100 User Manual Download Page 51](http://html1.mh-extra.com/html/frc/turbofoam-tfc100/turbofoam-tfc100_user-manual_2329200051.webp)
TFC100 Rev180215
51
Hose Sizes:
Hoses Provided by Installer
Standard Fittings are NPT (National Pipe Taper)
Use shortest hose runs possible for concentrate hose lines;
Pump input needs 10" minimum of hose for vibration absorption.
Figure L8. TFC200 Plumbing Two Tank System w/Manual ABF Selector
Standard All Pumps:
1/2" Female
Standard All Pumps:
1/2" Female
Standard All Pumps:
1/2" Male
Standard All Pumps:
3/4" Male
Clear Suction Hose
23" (584mm) Hg Vacuum; 50 PSI (3 bar)
1.6, 2.6 GPM Pumps:
3/4" (19mm) ID
3.5, 5.0, 6.2, 6.5 GPM Pumps: 1" (25.4mm) ID
Pressure Hose
500 PSI (34 bar)
Standard All Pumps: 1/2" (13mm) ID
Pressure Hose
500 PSI (34 bar)
Standard All Pumps: 1/2" (13mm) ID
Clear Suction/Pressure Hose
23" (584mm) Hg Vacuum; 500 PSI (34 bar)
1.6, 2.6 GPM Pumps:
3/4" (19mm) ID
3.5, 5.0, 6.2, 6.5 GPM Pumps: 1" (25.4mm) ID
Fitting Sizes:
Fittings Provided with System Kit
1.6 and 2.6 GPM Pumps:
3/4" Female
3.5, 5.0, 6.2, 6.5 GPM Pumps:
1" Female
1.6 and 2.6 GPM Pumps:
3/4" Male
3.5, 5.0, 6.2, 6.5 GPM Pumps:
1" Male
Standard All Pumps:
3/4" Female
Summary of Contents for Turbofoam TFC100
Page 69: ...TFC100 Rev180215 69 CONTROL MODULES Figure P1 TurboFoam Control Modules 6 7 5 4 3 2 1 ...
Page 81: ...TFC100 Rev180215 81 MANUAL ABF SELECTOR Figure P7 Manual ABF Selector 9 8 6 5 4 3 2 1 7 ...
Page 85: ...TFC100 Rev180215 85 NOTES ...
Page 86: ...TFC100 Rev180215 86 NOTES ...
Page 87: ...TFC100 Rev180215 87 NOTES ...
Page 88: ...TFC100 Rev180215 88 ...