Table 6. Fault Warning Codes
Code
TFC200/300/400
Message Display
Description
F01
FOAM A
LOW
A foam concentrate low
F02
FOAM B
LOW
B foam concentrate low
F03
FOAM A
EMPTY
A foam concentrate tank empty; control module to off mode
F04
FOAM B
EMPTY
B foam concentrate tank empty; control module to off mode
F05
SYSTEM
AT MAX
Request exceeds foam concentrate pump capacity
F01-F04: When tank float switches are used the codes P309 and P310 set the time delay between the tank
low fault warning (F01, F02) and the tank empty fault warning (F03, F04). When a TankVision Pro is
connected the tank low/tank empty information is provided over the datalink. The concentrate pump is
switched off when the tank empty goes active.
Preset Settings
The preset button allows the operator to go to a pre-programmed percent setting during operations.
The preset value shows in the % display.
Note:
The preset setting (selected when the
PRESET
button is pressed) can only be set to a program
enabled value. Refer to Programming Section for information on Set +/– Increment Value, codes
P118 and P119.
To access the preset setting program the discharge flow must be 0 (
FLOW
display shows 000).
1. Select A foam tank or B foam tank.
For dual tank systems. TFC200 set the manual ABF selector; TFC400 press the A/B button.
For single tank systems this is set with program code P312.
2. Press and hold
PRESET
button. (Continue to hold through step 4.)
Result: % display flashes the programmed setting.
3. Press the
+
and
–
buttons to change setting.
4. Release
PRESET
button.
Result: The new preset value is programmed.
Summary of Contents for Turbofoam TFC100
Page 69: ...TFC100 Rev180215 69 CONTROL MODULES Figure P1 TurboFoam Control Modules 6 7 5 4 3 2 1 ...
Page 81: ...TFC100 Rev180215 81 MANUAL ABF SELECTOR Figure P7 Manual ABF Selector 9 8 6 5 4 3 2 1 7 ...
Page 85: ...TFC100 Rev180215 85 NOTES ...
Page 86: ...TFC100 Rev180215 86 NOTES ...
Page 87: ...TFC100 Rev180215 87 NOTES ...
Page 88: ...TFC100 Rev180215 88 ...