Calibrate Discharge Flow Sensor (Password Code 1111)
Note:
Use a calibrated flow meter or Pitot gauge on the discharge under test as a reference.
When flowing water, ensure a constant pressure is maintained to obtain a steady flow rate.
For systems with multiple discharge flow sensors, calibrate each sensor separately.
Select a second reference flow rate and flow water for each discharge to verify the calibration. The flow rate
shown on the
FLOW
display should match the flow rate shown on the reference meter.
Once the system has been calibrated the System Restore function is used when a component is replaced.
(Refer to Programming Section.)
Single Sensor System
1. Enter password code 1111. (Refer to Password Protected Programs Section.)
Result: The message display shows
WATER CAL GPM
.
2. Press the
MENU
button.
Result: The
FLOW
display shows the flow rate with the last digit flashing.
3. Flow water through the discharge.
4. Set the flow rate shown on the
FLOW
display to match the flow rate shown on the reference meter.
Press the
+
and
–
buttons to change the digit.
Press the
PRESET
button to move the curser to the next digit.
5. Press and hold the
MENU
button for five (5) seconds to save and exit.
Result: The message display shows
UPDATING SYSTEM
. then
CAL DONE
.
Multi-Sensor System (w/Summing Box)
1. Enter password code 1111. (Refer to Password Protected Programs Section.)
Result: The message display shows
MULTIPLE FLOW CAL
.
2. Press the
MENU
button.
Result: The message display shows the ID name and sensor number.
3. Press the
+
and
–
buttons to change the ID name and sensor number.
4. Press the
MENU
button.
Result: The
FLOW
display shows the flow rate with the last digit flashing.
5. Flow water through the discharge.
6. Set the flow rate shown on the
FLOW
display to match the flow rate shown on the reference meter.
Press the
+
and
–
buttons to change the digit.
Press the
PRESET
button to move the curser to the next digit.
7. Press and hold the
MENU
button until display shows
CAL IN PROGRESS
to save new setting.
8. Return and repeat steps 3 through 7 or:
9. Press
PRESET
button to save and exit.
Result: The message display shows
UPDATING SYSTEM
then
CAL DONE
.
Summary of Contents for Turbofoam TFC100
Page 69: ...TFC100 Rev180215 69 CONTROL MODULES Figure P1 TurboFoam Control Modules 6 7 5 4 3 2 1 ...
Page 81: ...TFC100 Rev180215 81 MANUAL ABF SELECTOR Figure P7 Manual ABF Selector 9 8 6 5 4 3 2 1 7 ...
Page 85: ...TFC100 Rev180215 85 NOTES ...
Page 86: ...TFC100 Rev180215 86 NOTES ...
Page 87: ...TFC100 Rev180215 87 NOTES ...
Page 88: ...TFC100 Rev180215 88 ...