background image

19

Purging the line

•  If air is in the system, the lines must be purged of the air. If needed, this procedure should 

be done before the Line Stability Test.

•  Purge the line by dispensing from each fueling point starting with the dispenser furthest 

from the tank. The STP should be running the full time that the line is purged.

•  Purging of lines is required prior to performing the AUTO-LEARN

®

 process. Submersibles 

should operate prior to programming or prior to learning of lines. 

•  FE PETRO

®

 

Smart controllers can be put in bypass mode for the purpose of purging  lines by 

setting Pole 7 – Switch Bank 1 to ON.  (The best practice is to power off the controller prior 
to changing dip switch settings). This will allow submersible to run in Bypass mode for 10 
minutes.  If longer time is required simply reset controller (push reset button) for another 
10 minutes of bypass mode.

•  When needing to purging lines after the console is programmed for line leak detection and 

prior to the AUTO-LEARN

®

 process. Purging must be completed with the line testing disabled 

in the line programming section of Set-up parameters.  This will allow pumps to run without 
interruption from line leak software during purging. Once purging is complete re-enable 
testing under set-up parameters.

NOTE

: If purging is required after the lines have been learned, the same process is required to disable 

testing in setup parameters to allow a pump to run for purging purposes. 

Zero Offset

•  TS-LS500 AUTO-LEARN

®

 ELLD requires that the line reach 0 PSI prior to starting the learn 

process. 

•  Failure to follow this step can lead to improper pressure readings, an inability to fail a test 

properly and overall improper operation of the ELLD application. 

•  IF the line cannot reach 0 PSI when opening the needle valve and bleeding off the line 

pressure additional purging of line is required to remove air that is preventing the line to 
fully bleed off to 0 PSI.

Summary of Contents for TS-LS500

Page 1: ...TS LS500AUTO LEARN LINE LEAK DETECTION INSTALLATION GUIDE...

Page 2: ...and diesel fuel are present Working in such a hazardous environment presents a risk of severe injury or death if you do not follow standard industry practices and the instructions in this manual Befor...

Page 3: ...onsole Programming 8 AC Input Module 8 4 20mA Input Module 10 Relay Module 10 Turbine Pump Interface TPI Applications 12 Fuel Management Systems FMS Line Application Set Up 13 Line Status and Control...

Page 4: ...TS LS500 Functional Testing 30 Enabling Disabling Lines 32 Enabling Lines 32 Disabling Line Channels 32 Control Drawing 1 33 Control Drawing 2 34...

Page 5: ...AUTO LEARN technology to learn the characteristics decay curve of a calibrated 3 GPH leak as part of the line calibration process Definitions and acronyms AIM 4 20mA Analog Input Module Intrinsically...

Page 6: ...phon valve is installed at the discharge of the submersible pump the TS LSU500 transducer should be installed downstream of the valve to insure proper line pressure monitoring Site Requirements Minimu...

Page 7: ...should be located in the master STP In line check valves should NOT be used as the line leak detection will not be able to test beyond them Please see the STP manufacture about appropriate check and...

Page 8: ...500 transducers 2 Mount the TS LSU500 in the Leak Detector Port of the STP housing As outlined in the Transducer Installation Section above 3 The TS LSU500 wiring must enter the console in IS conduit...

Page 9: ...k Pressure Sensor BLK RED LS 500 Hazardous Location Class I Division 1 Group D Group IIA Zone 0 Non Hazardous Location Intrinsically Safe Conduit Blue TS LSU500 Junction Box Red Black Black Black Blac...

Page 10: ...ocal codes NOTE The explosion proof transducer needs to have explosion proof conduit to the head of the transducer 1 Pull the wiring through the explosion proof conduit that will be used for the TS LS...

Page 11: ...ally Safe Side of Console Red Explosion Proof Conduit LS 500E Explosion Proof Conduit 4 20mA EXP INPUT MODULE RUN ERR BLK RED Hazardous Location Class I Division 1 Group D Group IIA Zone 0 Non Intrins...

Page 12: ...es and set them accordingly per the site You will be prompted to enter the Administrator password when it is required NOTE Site setups vary depending on the products used and other equipment installed...

Page 13: ...annel and a low signal will deactivate the channel If set to LOW then the channel is inverted and will only become active when a signal is absent and inactive when a signal is present Action Select NO...

Page 14: ...ay channels The 10A relay module contains 6 relay channels Each relay is used by the console to turn a specific STP on or off in applications where Turbine Pump Interface TPI is not used Parameter Par...

Page 15: ...bmersible Pump Polarity Normal Logic OR Logic Physically Wired As Normally Open Number of inputs 4 Input 1 Type 4 20mA Input Module Channel Unleaded Transducer Input 2 Type AC Input Module Channel Dis...

Page 16: ...roller Enabled Yes Type Mag Eco Address 1 Group 0 Tank 1 Height 5 00 in Number of inputs 4 Input 1 Type 4 20 mA Input Module Channel Unleaded Transducer Input 2 Type AC Input Module Channel Dispenser...

Page 17: ...ween test in monthly testing sections of programming Product Enter Product name grade Enable Select Yes Enables line testing No there is no line testing in operation on this line Pressure Up Test Wait...

Page 18: ...SLLD Yes Product Unleaded Enabled Yes Pressure Up Test Wait Time 4 Sec Catch pressure Wait Time 2 Sec Dispenser Pressure Test Yes Gross Tests Enable Yes Monthly Tests Enable Yes Wait Period Between Pa...

Page 19: ...reens To get to the Line Status or Control screens go to FMS Status Lines or FMS Control Lines TS LS500 Status Screen The status of each line can be viewed at any time by navigating to the line status...

Page 20: ...ng out Thermal Green if waiting out thermal Gray if not Transducer Failure Red if the TS LS500 is not communicating with the transducer Pump On Green if the STP is on Pump Request The TS LS500 is atte...

Page 21: ...t Manually start a gross leak test Force Monthly Leak Test Manually start a monthly leak test Force an Annual Leak Test Manually start an annual leak test Learn Section Indicator Description Start Sto...

Page 22: ...al regulations NOTE The STP connected to the line being tested will need to be activated by lifting the appropriate product dispenser handle Verify that all STP s and pump controllers are installed ca...

Page 23: ...pass mode When needing to purging lines after the console is programmed for line leak detection and prior to the AUTO LEARN process Purging must be completed with the line testing disabled in the line...

Page 24: ...n 5 PSI 34 5 kPa in 5 minutes 3 If the pressure does change pressurize the line again by lifting the dispenser handle do not dispense and check again 4 If it does not change more than 5 PSI 34 5 kPa i...

Page 25: ...mming Guide p n 228180061 for information on gaining Administrator privileges NOTE Complete the Pre Operation Line Testing chapter prior to starting the Learn Process NOTE No dispensing can take place...

Page 26: ...ct Let the line pressure bleed down to 0 Make sure that the pressure reads 0 on the pressure gauge installed on the needle valve kit 3 Navigate to the line control screen on either the touch screen or...

Page 27: ...needle valve To clear the alarm navigate to the line control screen and choose reset alarm The console will ask Do you also want to enable this line Select OK If you select CANCEL the line will not b...

Page 28: ...al please see the T5 Series Programming Manual p n 000 2142 the T5 Series Operator s Guide p n 000 2151 the EVOTM 550 and EVOTM 5000 FMS Programming Guide p n 000 2173 the EVOTM 600 and EVOTM 6000 Pro...

Page 29: ...the condition still exists after reset the alarm will return A service visit may be required to identify and correct the condition WARNING Always REMOVE POWER from the console prior to installing rem...

Page 30: ...or detected Console software error Reboot console Air in line Console has sensed line pressure variations Investigate then Purge Line Starting at the Furthest Dispenser Not learned Learn Line FMS Cont...

Page 31: ...ressure Test Failed Pressure dropped to less than 7 5 PSI 52 kPa while dispensing Monitor line pressure using a pressure gauge investigate for leaks High Pump Pressure Pressure was above 50 PSI 345 kP...

Page 32: ...aks force leak test to verify Inadequate learning Line not properly bled to zero during learning Re learn the line follow procedures Air was not bled out of the line prior to learning Purge the line r...

Page 33: ...ssary to clear line alarm For more information about obtaining administrator access please see the T5 Series Programming Manual p n 000 2142 the T5 Series Operator s Guide p n 000 2151 the EVOTM 550 a...

Page 34: ...essure will be witnessed on web interface but Gross Test in Progress Failing is only populated on touch screen NOTE Calibrated Leak Generator will start allowing line pressure to gradually drop off as...

Page 35: ...start allowing line pressure to gradually drop off as fuel passes into approved container f System will disable pump on second consecutive failure roughly 5 8 minutes NOTE any dispensing between first...

Page 36: ...tton to enable the line Only while the line is enabled will it continuously monitor and test pressure levels by activating the STP as necessary Disabling Line Channels At the T5 Series EVOTM 600 or EV...

Page 37: ...33 Control Drawing 1...

Page 38: ...34 Control Drawing 2...

Page 39: ...Intentionally Blank...

Page 40: ...000 2145 r11...

Reviews: