8
TS-LS500 Setup (Console
Programming)
The following instructions are a guide to programming the Line Leak Detection portion in the ATG
console. The administrator password will be to edit set-up parameters. For instruction on FMS
programming, or how to obtain the Administrator access level, please refer to the T5 Series FMS
Programming Guide (p/n 000-2142), the EVO
TM
550 and EVO
TM
5000 FMS Programming Guide
(p/n 000-2173), or the EVO
TM
600 and EVO
TM
6000 Programming Guide (p/n 228180061).
Access the T5 Series FMS console (via the LCD touch screen or by the web) and navigate to the
Setup Menu, Go to each of the following parameters, shown in the next tables, and set them
accordingly per the site. You will be prompted to enter the Administrator password when it is
required.
NOTE:
Site setups vary depending on the products used and other equipment installed. Setup
information in the sections of this chapter depicts a typical site and are meant as examples only.
AC Input Module
One of the functions of the AC input module is to accept incoming dispenser hook signals.
The hook signal tells the console which product the dispenser is requesting, then turns the
appropriate Submersible Turbine Pump (STP) on using either a relay (from the relay board or
from the power supply board) or the turbine pump interface (TPI). The TS-LS500 is constantly
monitoring the pressure on the line, and testing accordingly. To perform tests properly, the
TS-LS500 needs to know when the pumps are being used by other applications.