72
Alarm/Warning
Device
Description
Recommended Actions
Short Circuit
TPI
The STP controller is
reporting a short circuit
condition.
Refer to the applicable Smart Controller
Installation guide for details.
SMTP Error
NONE Communication error with
the email set-up/server.
Troubleshoot Email setup with IT department.
SN2 Fuse Blown
ChannelSN2
2-Wire Sensor Module
fuse blown due to
unknown causes.
The fuses on the Sensor boards are non-
serviceable per UL listing standards. The module
must be replaced if the fuse is blown.
SN3 Fuse Blown
ChannelSN3
3-Wire Sensor Module
fuse blown due to
unknown causes.
The fuses on the Sensor boards are non-
serviceable per UL listing standards. The module
must be replaced if the fuse is blown.
SN3 Power
Short
AU_MODULE
3-Wire Sensor Module
drawing too much
current.
The module must be replaced if the fuse is
blown.
Sudden
Pressure Loss
Line
During a 45 minute quite
period the pressure was
seen to drop by a 2 times
the learned 3 gph slope.
Inspect all sumps for product. Refer to “LS500
Auto Learn Line Leak Detection Installation
& User’s Guide” FFS 000-2145 for more
information.
Sump empty
SENSOR
Sump full
SENSOR
Discriminating Sensor has
detected the containment
is full
Check containment for collection of fluid.
Troubleshoot source of the leak.
Tank delivery
detection
canceled
TANK
Tank in service
mode
TANK
Tank product
density high
limit exceeded
TANK
Tank product density high
limit exceeded
Verify programming is set correctly. Then use
time stamp of alarm to investigate cause.
Tank product
density low
limit exceeded
TANK
Tank product density low
limit exceeded
Verify programming is set correctly. Then use
time stamp of alarm to investigate cause.
Tank Sentinel
Mode Alarm
TANK
The ATG has detected a
theft of fuel during non-
business hours.
Verify programming is set correctly. Then use
time stamp of alarm to investigate theft.
Tank Water/
Phase Sep Float
Disabled
Tank
The Phase Separation
Water Float has been
disabled in setup
Verify Phase Separation Water Float level and
enable the float in setup.
TC zero error
TANK
Temperature
compensation
error
TANK
Temperature
error
Tank
Special Probe RTD
temperature error
detected.
Verify correct RTD table programming. If
problem still exists, suspect wiring or faulty
probe.
Temperature
range error
TANK
Temperature
reference error
TANK
Summary of Contents for EVO 600
Page 1: ...EVOTM 600AND EVOTM 6000 AUTOMATICTANK GAUGES PROGRAMMING GUIDE ...
Page 6: ......
Page 24: ...18 Intentionally Blank ...
Page 28: ...22 Intentionally Blank ...
Page 56: ...50 Intentionally Blank ...
Page 66: ...60 Intentionally Blank ...
Page 82: ...76 Intentionally Blank ...
Page 84: ...78 Intentionally Blank ...
Page 85: ...79 Intentionally Blank ...
Page 86: ...228180061 r1 ...