73
Alarm/Warning
Device
Description
Recommended Actions
Time source
error
NONE
Too few bytes
error
TANK
Too many floats
TANK
# of floats detected on
probe is more than what
is programmed in the ATG
Verify configuration programming is set to the
actual number of floats on the probe.
Ullage error
Tank
Ullage reported has
exceeded tank capacity.
Check for proper probe and tank programming
at the console. If programming is correct,
inspect the probe to ensure that the float is
not stuck in the riser or obstructed. Bring the
probe inside and wire directly to the gauge
to eliminate possible problems with the field
wiring.
Unbalanced
Load
TPI
The STP controller is
reporting an unbalanced
load condition.
Refer to the applicable Smart Controller
Installation guide for details.
Unbalanced
Voltage
TPI
The STP controller is
reporting an unbalanced
voltage condition.
Refer to the applicable Smart Controller
Installation guide for details.
Under Load
TPI
The STP controller is
reporting an underload
condition.
Refer to the applicable Smart Controller
Installation guide for details.
Under Voltage
TPI
The STP controller is
reporting a voltage level
under 200VAC.
Refer to the applicable Smart Controller
Installation guide for details.
Unexpected
reset
NONE
Unknown
NONE
Unknown Fault
TPI
The STP controller is
reporting an unknown
fault code.
Check fault condition on Smart controller
and contact FFS Technical Services for more
information
Unstable probe
Tank
LL Liquid Level probes can
send inconsistent data
back to console.
Check for proper probe programming at the
console and inspect wire connections at the
probe. If the problem persists, contact FFS
Technical Services for support.
Vapor detected
SENSOR
A discriminating sensor
has detected vapor.
Check location where sensor detected vapor.
Watchdog reset
NONE
Water present
SENSOR
A discriminating sensor
has detected the liquid
present is water.
Check containment for collection of water.
Troubleshoot source of the leak.
Water volume
error
Tank
Water volume has
exceeded tank capacity.
Check for proper probe and tank programming
at the console. If programming is correct,
inspect the probe to ensure that the colored
water float is on the bottom.
Web server
error
NONE
Wire Sensor
Alarms
Summary of Contents for EVO 600
Page 1: ...EVOTM 600AND EVOTM 6000 AUTOMATICTANK GAUGES PROGRAMMING GUIDE ...
Page 6: ......
Page 24: ...18 Intentionally Blank ...
Page 28: ...22 Intentionally Blank ...
Page 56: ...50 Intentionally Blank ...
Page 66: ...60 Intentionally Blank ...
Page 82: ...76 Intentionally Blank ...
Page 84: ...78 Intentionally Blank ...
Page 85: ...79 Intentionally Blank ...
Page 86: ...228180061 r1 ...