16
4. Control relay setup
A wide range of setting options are pro-
vided to enable the reactive power con-
trol relay to be used in the widest possi-
ble way. To simplify matters the control
relay is set to standard values in the fac-
tory (see table 1 below).
This means that the user mostly only
needs to change the target power factor.
The setup mode can be reached from
any of the control relay’s operating
modes.
Setup
code
Significance
Standard
values
Setting range
-1-
Target power factor
ind 1.00
From inductive o,85 to o,99 and
from inductive 0.85 to 1.00
in steps of 0.01
-2-
Maximum harmonic over-
current until the alarm is
activated
1.30
From 1.05 times to 1.95 times the
fundamental wave current or OFF
in steps of 0.05
-3-
-Alarm output on contact 6
and contact 12 respectively
-switch on or off alarm E5
OFF
no alarm
E5
OFF or On
with or without alarm E5
(see section 4.3)
-4-
Automatic determination of
response current
On
OFF or On
-5-
Manual setting of
response current
2.00
from 0.02 to 2
in steps of 0.01
-6-
Relative value of the stage
1.0 for each
switch
output
Optional for each switch
output the value 0 to 16
in steps of 1.0
-7-
Service:
---
Measuring (only the fundamental
frequency components):
- Active current
- Reactive current
- Apparent current
Table 1: Programmable values