Figure 6: Connection in special cases
2.10 Connection in special cases
The type of connection shown above
should be used if the voltage between
the phase conductors does not exceed
240VAC.
The following general principles apply:
If the terminal ”Meas” remains unused,
the voltage for terminals ”L” and ”N” must
be connected to a phase conductor and
to the neutral conductor.
If the terminal ”Meas” is used, the voltage
for terminals ”Meas” and ”L” must be
connected each to a phase conductor.
For all types of connections (figure 3 to 6)
it is also possible to connect the current
transformer in phase conductors L2 or
L3. In this case, the voltage connections
to the phase conductors should be ex-
changed accordingly.
If the control relay operates with auto-
matic response current recognition, con-
nection errors would be reported.
If response current recognition is deacti-
vated, then an error in the connection will
lead to functional errors during subse-
quent operation.