Annex PRELIMINARY
User Manual EML1101
19.5 Terminal assignments
Terminal No.
Description
Notes
1
FRAKO Starkstrombus
channel A
2
FRAKO Starkstrombus
channel B
3
FRAKO Starkstrombus
GND
4
Add-on bus channel A
5
Add-on bus channel B
6
Add-on bus GND
Can be connected to ground via jumper
7
Active pulse input1
+ (For connection to a potential-free contact
against ground)
8
Active pulse input2 / Reset input self
adjusting target maximum demand
+ (For connection to a potential-free contact
against ground)
9
Reactive pulse input
+ (For connection to a potential-free contact
against ground)
10
Time pulse input
+ (For connection to a potential-free contact
against ground)
11
Profile input 1
+ (for connection a potential-free contact against
ground)
12
Profile input 2
+ (For connection a potential-free contact against
ground)
13 Ground
- (Ground connection for all inputs)
14 Ground
- (Ground connection for all inputs)
15 Load
1
Common
16 Load
connection
NC contact
17 Load
connection
NO contact
18 Load
2
Common
19 Load
connection
NC contact
20 Load
connection
NO contact
21 Load
3
Common
22 Load
connection
NC contact
23 Load
connection
NO contact
24 Load
4
Common
25 Load
connection
NC contact
26 Load
connection
NO contact
27
Hardware alarm indication contact
Common
with hardware version 1.3 upwards.
28
Hardware alarm indication contact
NO contact (closed on alarm)
with hardware version 1.3 upwards.
29 Alarm
contact
Common
30 Alarm
contact
NC contact (open on alarm)
31 Alarm
contact
NO contact (close on alarm)
32
Emergency load shedder power supply
Pole
33
Emergency load shedder connection
NO contact
34
Emergency load shedder connection
NC contact
35
36
37
Power connection L
230VAC
38
Power connection N
39
Power connection PE
46