Annex PRELIMINARY
User Manual EML1101
19.2 Table of settings
Item Designation
Description
Units Value
range
Basic settings
1 Target
maximum
demand P1, P2,
P3, P4
Set target maximum demand Profiles 1, 2,
3, 4
kW/MW 0-6500
2
Current target
maximum demand
P1, P2, P3, P4
Current target maximum demand Profiles
1, 2, 3, 4 with activated self adjusting
target maximum demand
kW/MW 0-6500
3
Initial value
target maximum
demand P1, P2,
P3, P4
Initial value target maximum demand
Profiles 1, 2, 3, 4 with activated self
adjusting target maximum demand
kW/MW 0-6500
4
Upper limit
target maximum
demand P1, P2,
P3, P4
Upper limit target maximum demand
Profiles 1, 2, 3, 4 with activated self
adjusting target maximum demand
kW/MW 0-6500
5
Peak power P1,
P2, P3, P4
Set peak power Profile 1, 2, 3, 4
kW/MW 0-6500
6
Control delay
Pause between individual switchings
s
1-60
7 Control
application point
As of how many %
Σ
P of the set target
maximum demand control is to become
fully effective.
% 0-75
8 Emergency
mode
active at X%
Application pint of the emergency mode.
%
10-80
Other settings
1
Measuring period
Pre-set time by electricity company
10,15,30,60
2
Counter constant.
P_act1,
P_act2
Counter constant referenced to 1kWh
1-99999
3 Voltage
transfer
P_act1,
P_act2,
Q
Voltage transformer ratio
U_primary/U_secondary
1-9999
4 Current
transfer
P_act1,
P_act2,
Q
Current transformer ratio
I_primary/I_secondary
1-9999
5 Counter
constant.
Q
Counter constant referenced to 1kWh
1-99999
6 Average
over
(P_act1,
P_act2, Q)
Number of active pulses for mean value.
Only affects display.
1-99
7
Cosphi Alarm at
Cosphi < XX %
Limiting value for cosphi alarm.
0.00 - 0.99
8
Bus Address
Address of EML at FRAKO
Starkstrombus
9-125
9 Auto
winter/summer
time changeover
Activates / deactivates automatic setting of
summer and winter time
Yes/
No
40