24
SINGLE PHASE, IGP/IGPH/IGPHR AUTOMATIC GRINDER
Wiring Diagram
1 PHASE
IGP-A/IGPH-A/IGPHR-A GRINDER PUMP
208/230 VAC
PUMP POWER CABLE
BL
UE
OR
ANGE
BR
OWN
RED
RED
/BL
ACK
BL
ACK
12 AWG PUMP CABLE
125 FT MAX
18 AWG
FLOAT
CABLE
PANEL GRD
L1
L2
N
T1
T2
1
2
3
4
5
6
PUMP
MOTOR
LS1
PUMP OFF
LS2
PUMP ON
LS3
ALARM
CONTROL PANEL
515352, 515363
208/230 VAC 115 VAC
1 PHASE - 60 HERTZ POWER SUPPLY
PUMP
OFF FLOAT
PUMP
ON FLOAT
HIGH LEVEL
ALARM FLOAT
BL
ACK
BL
ACK
BL
ACK
WHITE
WHITE
WHITE
GREEN
WHITE
BL
ACK
TANK JUNCTION BOX
MOUNTED IN TANK DRY WELL
NOTE:
This is a control drawing only and does not reflect the actual locations of cable penetrations.
1. Follow National Electric Code NEC/NFPA/ANSI 70 and local regulations when installing all wiring.
2. This system is meant to be used with approved components only.
3. Main power disconnect is to be provided by installer.
4. Torque large field wiring terminals to 35 in-lbs and small field wiring terminals to 12 in-lbs.
5. Field wiring must be 60 °C copper wire minimum.
6. Level switches must be rated a minimum of 2 Amps at 120 V.