Battery voltage detected inconsistent
84
AC input voltage and frequency detected are inconsistent
85
AC output current unbalanced
86
AC output mode setting inconsistent
Warning code
Event
Audible alarm
Flashing icon
01
Fan is locked when inverter
is on
Beeps three times every second
02
Overtemperature
None
03
Battery is over-charged
Beeps once every second
04
Low battery
Beeps once every second
07
Overload
Beeps once every 0.5 second
10
Output power derating
Beeps twice every 3 seconds
Battery equalization is
occurring
None
Battery is not connected
None
Warning indicators
Problem
What to do
Fault code
Explanation/possible
cause
60
Current feedback into the
inverter is detected
1. Restart the inverter.
2. Check if L/N cables are not connected inversely in all inverters.
3. For parallel systems in single phase, make sure the share
current cables are connected between all inverters.
For three-phase systems, make sure the share current cables
are connected between all units on the same phase, and not
connected to any units on the other phases.
4. If the problem remains, contact your installer
71
The firmware version of
each inverter is not the
same
1. Check the version of each inverter via LCD setting and make
sure the CPU versions are the same. If they differ, update all
inverter firmware to the same version (contact your instraller).
2. If the problem persists after updating, contact your installer
72
The output current of each
inverter is inconsistent
1. Check if the share current cables are correctly connected and
restart the inverters.
2. If the problem remains, please contact your installer