Ver. 2.0
Oven Clearances
It is essential to maintain clearance space between the oven
components and any combustible material, such as walls
and ceilings. Failure to maintain these clearances can result
in fire.
Combustible Wall Clearance
The oven must have a minimum 1" (25 mm) clearance to
combustibles from all sides, and 14" (35 cm) clearance to
combustibles from the top.
If building materials will contact the oven, they must be
completely noncombustible. Please note that standard
drywall (or sheet rock) is considered a combustible.
The area directly above the doorway and 6" (15 cm) to
each side of the doorway must be covered with non-
combustible material.
Non-combustible construction may contact the oven and
must then maintain 1" (25 mm) clearance to combustibles.
If the space between the legs of the stand is used for wood
storage, it is recommended that it be a covered container
or box to prevent the possibility of sparks or embers from
making contact with the stored wood. An 8-1/2" (eight
and one-half inch) (21 cm) air space clearance is required
between the bottom of the oven and any wood storage
container.
Floor Hearth Extension
The minimum floor hearth extension areas from the oven
door opening to combustible floors are as follows:
☐ 30" (76 cm) to each side of the door opening
☐ 36" (91 cm) in front of the door opening