Group 16 LCD Keypad Parameters
Param.
#
Parameters
Setting Range
Default
Unit
Control Mode
Notes
V/F
SLV
PMSLV
16-05
LCD Backlight
0–7
5
-
16-07
Copy Function
0: Do not copy parameters
1: Read AC Drive parameters and store
parameters settings in the operator.
2: Write the operator parameters to the
AC Drive.
3: Compare operator parameters
against AC Drive.
0
-
16-08
Parameter Read Allow
0: Do not allow to read AC Drive
parameters or save them to the
operator.
1: Allow to read AC Drive parameters
and save to the operator.
0
-
16-09
Operator Removed
0: Continue operation when LCD
operator is removed.
1: Display fault when LCD operator is
removed
0
-
Group 17 Automatic Tuning Parameters
Param.
#
Parameter Name
Setting Range
Default
Unit
Control Mode
Notes
V/F
SLV
PMSLV
17-00
Automatic Tuning Mode
0: Rotation Auto-tuning
1: Static Auto-tuning
2: Stator Resistance Measurement
3: Reserved
4: Loop Tuning
5: Rotation Auto-tuning Combination
(item: 4+2+0)
6: Static Auto-tuning Combination
(item: 4+2+1)
V/F: 2
SLV: 6
-
X
(note)
17-01
Motor Rated Output
Power
0.00–600.00
KVA
KW
X
(note)
17-02
Motor Rated Current
0.1–1200.0
KVA
A
X
(note)
17-03
Motor Rated Voltage
240V: 50.0–240.0
KVA
V
X
480V: 100.0–480.0
KVA
17-04
Motor Rated Frequency
4.8–599.0
KVA
Hz
X
17-05
Motor Rated Speed
0–24000
KVA
rpm
X
(note)
17-06
Motor Poles
2–16(Even)
4
Pole
X
17-08
Motor no-load Voltage
240V: 50–240
-
V
X
(note)
480V: 100–480
17-09
Motor Excitation Current
0.01–600.00
-
A
X
X
(note)
17-10
Automatic Tuning Start
0: Disable
1: Enable
0
-
X
*1:
Parameter can be changed while running.