4-83
03-16
: Output Current detection delay time
ON: Output current has to rise above specified level (03-15) for time specified in 03-16.
OFF: Output current has to fall below specified level (03-15) for time specified in 03-16.
03-16
Constant
100 msec
03-15
03-11
Relay Output
ON
I : Load current
100%
T
03-17
Mechanical Braking Release Level Default: 0
Range
【
0.00–20.00
】
Hz
03-18
Mechanical Braking Set Level Default: 0
Range
【
0.00–20.00
】
Hz
When 03-11=14, when the output frequency is greater or equal to the value set in 03-18 (Brake Set Level) during
acceleration, the relay output will activate.
When 03-11=14, when the output frequency falls below the value set in 03-17 (Brake Release Level) during
deceleration, the relay output will de-activate.
When 03-18 ≤ 03-17, the following sequence applies:
RUN
STOP
ON
OFF
03-17
03-18
T
Hz
RUN
Note:
If the maximum output frequency of motor is over 300Hz, the frequency resolution is changed to 0.1Hz.