Operating Manual CMGZ 622
48
Offset output
Applies to:
Unwind brake
Use:
If the brake is activated although the controller gives no signal to the
brake, the faulty brake torque can be compensated here. The value
stored here is active only if the controller is enabled.
„10%“ means 10% of the maximum current value (refer to parameter
Current limit
).
Range:
0.1
to
50.0
Default:
0.0
Increment:
0.1
Unit:
[%]
Current limit
Applies to:
Unwind brake
Use:
This parameter defines the range for the output signal. „80%“ refers
to „±8V“ or „0...8V“ or „0...16mA“ or „4...16.8mA“, depending on
parameter
Output config
. Due to that, a current limitation for the
brake power can be realized indirectly.
For the CMGZ.B with integrated brake amplifier (optional) this
parameter must be set according to the maximum current of the
brake used. „100%“ refers to a maximum current of 2.0A; „87.5%“
refers to 1.75A max; „40%“ refers to 0.8A max, and so on.
Range:
10.0
to
100.0
Default:
100.0
Increment:
0.1
Unit:
[%]
Output limit
Applies to:
Unwind drive
Winding drive
Line drive
Use:
This parameter defines the range for the output signal. „80%“ refers
to „±8V“ or „0...8V“ or „0...16mA“ or „4...16.8mA“, depending on
parameter
Output configuration
.
Range:
0.1
to
100.0
Default:
100.0
Increment:
0.1
Unit:
[%]