Operating manual BMGZ 600A
26
fig. 24: State diagram BMGZ620A
B600022e
7.3
Setting the Installation-specific Parameters
For correct calculation of the flow rate, the following parameters must be set or
checked during initial operation (refer to „8. Parametrization“):
Belt length roller 1
Diameter roller 1
Pulses roller 1
Distance roller 1
Nominal force roller 1
Speed detection roller 1
Speed belt roller 1
(if parameter
Speed detection roll 1
is set to „none“
the speed will be 1m/s)
Using a evaluation electronic unit BMGZ620A (2 measuring rollers), the
parameters above must be set also for the 2
nd
roller.
Note
The parameters above have direct influence to the accuracy of the belt scale. If
the values differ from the real installation conditions, a useful weighing result is
not available. Without inputting and checking of those parameters, the belt
scale should not be set into operation!