www.fmiproducts.com
112127-01C
9
ventinG instaLLation
WARNING: Read all instruc-
tions completely and thoroughly
before attempting installation.
Failure to do so could result in
serious injury, property dam
-
age, or loss of life. Operation of
improperly installed and main
-
tained venting system could
result in serious injury, property
damage, or loss of life.
NOTICE: Do not seal termina-
tion cap to pipe. Cap must be
removable for servicing vent
system.
NOTICE: Failure to follow these
instructions will void the war-
ranty.
INSTALLATION PRECAUTIONS
Consult local building codes before begin-
ning the installation. The installer must make
sure to select the proper vent system for
installation. Before installing vent kit, the in-
staller must read this stove and burner system
manual and vent kit instructions.
• Wear gloves and safety glasses for protec
-
tion
• Use extreme caution when using ladders
or when on roof tops
• Be aware of electrical wiring locations in
walls and ceilings
The following actions will void the warranty
on your venting system:
• Installation of any damaged venting com
-
ponent
• Unauthorized modification of the venting
system
• Installation of any component part not
manufactured or approved by FMI PROD-
UCTS, LLC
• Installation other than as instructed by
these instructions
WARNING: This gas stove
with burner system and vent as
-
sembly must be vented directly
to the outside. The venting sys
-
tem must NEVER be attached to a
chimney serving a separate solid
fuel burning appliance.
WARNING: Horizontal sec-
tions of this vent system require
a minimum clearance of 2" from
the top of the pipe and 1" mini
-
mum to the sides and bottom.
Vertical sections of this system
require a minimum of 1" clear
-
ance to combustible materials
on all sides of the pipe.
INSTALLATION PLANNING
There are two basic types of direct-vent
installation:
• Horizontal Termination
• Vertical Termination
It is important to select the proper length
of vent pipe for the type of termination you
choose. It is also important to note the wall
thickness.
For Horizontal Termination:
Select the
amount of vertical rise desired. The horizontal
run of venting must have 1/4" rise for every
12" of run towards the termination.
WARNING: Never run the
vent pipe downward as this may
cause excessive temperatures
which could cause a fire.
You may use up to two 90° elbows on any
single horizontal run of vent pipe in this
configuration. See
Horizontal Termination
Configurations
, and Figures 17 and 19 on
page 12 and 13.