ventinG instaLLation

Continued

grade (basement applications), you must 
provide proper drainage to prevent water 
from entering the snorkel termination (see 

Figure  11).  Do  not  back  fill  around  the 

snorkel termination.

2.  Vent pipes and fittings have special twist-

lock connections. Assemble the desired 
combination of pipe and elbows to the ap-
pliance adaptor with pipe seams oriented 

towards the wall or floor.

 

Twist-lock  Procedure:

  The  female 

ends of pipes and fittings have 4 locking 

lugs (indentations). These lugs will slide 
straight into matching slots on the male 

ends of adjacent pipes and fittings. Push 

pipe sections together and twist one sec-
tion clockwise approximately one-quarter 
turn until the sections are fully locked (see 
Figure 12). 

Note: Horizontal runs of vent 

must be supported every 3 feet. Use wall 
straps for this purpose.

3.  Attach vent pipe assembly to the burner 

system. Set stove in front of it’s perma-
nent  location  to  insure  minimum  clear-
ances. Mark the wall for a 10" (25.4 cm) 
square hole (for noncombustible material 
such  as  masonry  block  or  concrete,  a 

1

/

2

" (19.1 cm) diameter hole is accept-

able). See Figure 13. The center of hole 
should line up with the center line of the 

horizontal rigid vent pipe. Cut a 10"x10" 

(25.4 cm x 25.4 cm) square hole through 
combustible exterior wall (7 

1

/

2

" [19.1 cm] 

diameter hole if noncombustible). Frame 
as necessary (see Figure 13).

4. 

Noncombustible  Exterior  Wall:

 Apply 

a bead of non-hardening mastic around 
the outside edge of the vent cap. Position 
the  vent  cap  in  the  center  of  the  7 

1

/

2

(19.1 cm) hole on the exterior wall with 
the  arrow  on  the  vent  cap  pointing  up. 
Attach the vent cap with four wood screws 
provided (see Figure 14, page 12). 

Note: 

Replace the wood screws with appropri-
ate fasteners for stucco, brick, concrete, 
or other types of siding.

 WARNING: Do not recess vent 

termination in to any wall. This 

will cause a fire hazard.

Figure 11 - Snorkel Termination with 

Drainage Pipe

Snorkel

Adequate 
drainage 

12" Minimum

(30.5 cm)

Vent Opening 

Noncombustible Wall

Figure 12 - Vent Pipe Connections

Female Locking Lugs

Male 
Slots

Vent Pipe

Figure 13 - Vent Opening Requirements

Summary of Contents for Natural Gas Burner System SDVBND

Page 1: ...s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the...

Page 2: ...arbon monoxide poisoning DANGER Carbonmonoxide poisoning may lead to death This appliance complies with the currentANSI Z21 88 as a Vented Gas Fireplace Heater and is listed and tested by the PFS Corp...

Page 3: ...This stove reaches high tem peratures Keep children and adults away from hot surface to avoid burns or clothingignition Stove will remain hot for a time after shutdown Allow surface to cool before to...

Page 4: ...t Opening Glowing Embers Grate Assembly Rear Cover Cast Iron Stove Body Lava Rock Cast Iron Stove Body Piezo Ignitor Control Valve Log Set Stove Front Immediately call a qualified service person to ar...

Page 5: ...WARNING A qualified in staller or service person must installstoveandburnersystem Follow all local codes CAUTION Thisstovecreates warm air currents These cur rentsmoveheattowallsurfaces next to stove...

Page 6: ...reattach back panel later 5 Remove bubble wrapped log set rod and screen from stove Remove all protective packaging applied for shipment 6 Check heater for any shipping damage If heater is damaged cal...

Page 7: ...ce between vent pipes and combustible materials is 1 2 5 cm except where stated otherwise Do not recess venting terminations into a wall or siding Install horizontal venting with a 1 4 rise for every...

Page 8: ...minimum L clearance above paved side walk or a paved driveway located on public property 84 213 3 cm minimum M clearance under veranda porch deck 12 30 5 cm minimum N clearance above a roof shall ext...

Page 9: ...tem Installation of any component part not manufactured or approved by FMI PROD UCTS LLC Installation other than as instructed by these instructions WARNING This gas stove with burner system and vent...

Page 10: ...ide of a building A chase is not required for such venting NOTICE Treatment of firestops and construction of the chase may vary from building type to building type These instruc tions are not substitu...

Page 11: ...re minimum clear ances Mark the wall for a 10 25 4 cm square hole for noncombustible material such as masonry block or concrete a 7 1 2 19 1 cm diameter hole is accept able See Figure 13 The center of...

Page 12: ...yl Siding Away to Fit Standoff Wood Screw Bolt Standoff Vent Cap Apply Mastic to All Four Sides Vent Cap Horizontal Termination Interior Wall Surface Interior Wall Firestop Combustible Exterior Wall O...

Page 13: ...ax 63 min 49 max 86 min 96 max 91 min 20 max Figure 18 Horizontal Termination Configuration for Venting Using Three 90 Elbows Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 6 min 4...

Page 14: ...reach from the burner system flue up through the firestop Be sure all pipe and elbow connections are fully twist locked see Figure 12 page 11 3 Cut a hole in the roof using the locat ing hole as a cen...

Page 15: ...nd into roof sheathing 4 Using tin snips cut support box from top corners down to roofline and fold resulting flaps over roof sheathing see Figure 23 Apply a bead of nonhardening mastic around top edg...

Page 16: ...6 min 4 max 7 min 6 max 8 min 8 max 20 max 8 max Figure 25 Vertical Venting Configuration Using Three 90 Elbows with Two Horizontal Runs Note Install restrictor into 4 collar of burner system as show...

Page 17: ...ystem has been tested and approved for operation at altitudes from 0 2000 ft When installing this stove at an elevation above 2000 feet you may need to decrease the input rating by changing the existi...

Page 18: ...rictor 7 12 Adjustable Coaxial Pipe 6 Pipe Adaptor 12 Coaxial Pipe 4 Coaxial Pipe Firestop Decorative Trim Plate Roof Flashing Storm Collar and 18 Screws Number Description P 47 12 K 12 Black Coaxial...

Page 19: ...tor notsupplied Installtheexternal regulator between the burner system and propane LP supply Figure 28 External Regulator with Vent Pointing Down Propane LP Only Propane LP Supply Tank External Regula...

Page 20: ...off Valve with 1 8 NPT Tap 3 Minimum LP From External Regulator 11 W C to 14 W C Pressure Approved Flexible Gas Line Cap Pipe Tee Nipple Joint Sediment Trap Drip Leg Natural From Gas Meter 5 W C to 10...

Page 21: ...meter to equipment shutoff valve see Figure 32 for propane LP or Figure 33 for natural gas Apply noncor rosive leak test solution to all gas joints Bubbles forming show a leak Correct all leaks at on...

Page 22: ...e is attached to the underside of the burner system assembly 2 Disconnect from the valve the wires run ning from the ON OFF switch 3 Connect one terminal of the wire for the wall thermostat to the THT...

Page 23: ...front panel on stove body CAUTION Do not operate this burner system with a bro ken glass door panel or without the glass door panel securely in place For replacement part information see Replacement P...

Page 24: ...hes in the bottom of log fit over the grate see Figure 39 3 Rest log 2 large front log on the pins on the front part of grate see Figure 40 4 Place log 3 crossover log onto rear and front logs Make su...

Page 25: ...on of front burner and along space between burner and grate prongs see Figure 43 This will create the glowing ember appearance as the flame touches the ember material Do not block air slots by using t...

Page 26: ...ve Gas Control Knob Piezo Ignitor For your safety read before lighting WARNING If you do not fol low these instructions exactly a fire or explosion may result causing property damage per sonal injury...

Page 27: ...minute Turn control knob to ON position Adjust flame adjustment knob anywhere be tween HI and LO Slide the selector switch to the REMOTE position see Figure 45 Note The burner may light if hand held r...

Page 28: ...ling Call a qualified service person to readjust the pilot if necessary The height of the thermopile must be 3 8 to 1 2 above the pilot flame as shown in Figure 46 The flame from the pilot burner must...

Page 29: ...lacing Glass Door page 23 for instructions for replacing glass door WARNING Do not operate burnersystemwiththeglassdoor removed cracked or broken CLEANING AND MAINTENANCE Continued Pilot and burners R...

Page 30: ...ing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor Nut is located behind the mounting bracket 4 Replace ignitor cable 5 Replace piezo ignitor 6 Replace pilot assembly 7 Replace pilot assem...

Page 31: ...pile leads discon nected or improperly con nected 4 Thermopile is defective 1 Clean burner see Cleaning and Maintenance page 28 or replace burner orifice 2 Contact local propane LP or natural gas comp...

Page 32: ...ked with any type of material 3 Follow venting configuration instructions on pages 12 thru 16 Burner system produces a clicking ticking noise just after burners are lit or shut off 1 Metalexpandingwhi...

Page 33: ...as leak See Warning statement page 37 1 Locate and correct all leaks see Checking Gas Connec tions page 20 Dark residue on logs or inside of burner system 1 Improper log placement 2 Air holes at burne...

Page 34: ...5 W C Minimum Inlet Supply Pressure 5 W C Dimensions HxWxD 27 x 21 1 2 x 18 68 6 x 54 6 x 45 7 cm SDVBPD Rating 20 000 28 000 Btu Hr Gas Type Propane LP Gas Manifold Pressure 10 W C Minimum Inlet Sup...

Page 35: ...propane LP gas to natural gas PcBv NS Conversion Kit For natural gas models Allows burner system to be converted from natural gas to propane LP gas Purchase these accessories from your local dealer I...

Page 36: ...www fmiproducts com 112127 01C 36 Parts Models SDVBND and SDVBPD TPTH TP TH 4 19 20 21 23 26 1 26 4 26 2 26 3 6 24 4 25 4 1 28 28 4 7 8 9 18 10 11 13 12 15 16 17 4 2 3 22 27 14 4 5 22 23...

Page 37: ...iezo 1 18 107014 01 Center Cast Stove Top Grate 1 19 14597 14598 Burner Natural Burner Propane LP 1 1 20 104506 16 104506 17 Orifice Natural Orifice Propane LP 1 1 21 14499 Brass Elbow 1 22 14264 Bras...

Page 38: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Page 39: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Page 40: ...s product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic ma...

Reviews: