background image

BRUCIATORI DI GAS A DUE STADI PROGRESSIVI / MODULANTI 

CON CAMMA MECCANICA

PROGRESSIVE/MODULATING TWO-STAGE GAS BURNERS 

WITH MECHANICAL CAM

ITALIANO

Manuale istruzioni per l'installazione, 

l'uso e la manutenzione

IT

Installation, use and maintenance ins-

truction manual

EN

TBG 1600 MC

ISTRUZIONI ORIGINALI (IT)

ORIGINAL INSTRUCTIONS (IT)

0006160218_201701

Summary of Contents for TBG 1600 MC

Page 1: ...PROGRESSIVE MODULATING TWO STAGE GAS BURNERS WITH MECHANICAL CAM ITALIANO Manuale istruzioni per l installazione l uso e la manutenzione IT Installation use and maintenance ins truction manual EN TBG 1600 MC ISTRUZIONI ORIGINALI IT ORIGINAL INSTRUCTIONS IT 0006160218_201701 ...

Page 2: ......

Page 3: ...4 Descrizione del funzionamento 15 Descrizione del funzionamento della modulazione 16 Accensione e regolazione 17 Misurazione della corrente di ionizzazione 20 Schema di regolazione testa di combustione e distanza disco elettrodi 20 Apparecchiatura di comando e controllo per bruciatori a gas LME73 21 Particolare motore SQM 53 di comando modulazione per regolazione cammes 22 Regolazione aria sulla ...

Page 4: ...YR RiNOx Spark Sparkgas TBG TBL TS IBR IB Variante LX per basse emissioni NOx rispettano i requisiti minimi imposti dalle Direttive Europee 2009 142 CE D A G 2004 108 CE C E M 2006 95 CE D B T 2006 42 CE D M e sono conformi alle Norme Europee prEN 676 2012 gas e misti lato gas prEN 267 2012 gasolio e misti lato gasolio EN 60335 1 2012 01 EC 2014 01 tutti i bruciatori Cento 12 Gennaio 2015 Direttor...

Page 5: ...ta di produzione dell apparecchio mese anno sono in dicati sulla targa identificazione bruciatore presente sull appa recchio L apparecchio non è adatto a essere usato da persone bam bini compresi le cui capacità fisiche sensoriali o mentali siano ridotte oppure con mancanza di esperienza o di conoscenza l uso dell apparecchio è consentito a tali persone solo nel caso in cui possano beneficiare att...

Page 6: ...o dalla loro sede Rendere innocue quelle parti che potrebbero essere poten ziali fonti di pericolo AVVERTENZE PER L AVVIAMENTO IL COLLAUDO L USO E LA MANUTENZIONE L avviamento il collaudo e la manutenzione devono essere ef fettuati esclusivamente da personale professionalmente qualifi cato in ottemperanza alle disposizioni vigenti Fissato il bruciatore al generatore di calore accertarsi durante il...

Page 7: ... dell impianto sia idonea alla potenza assorbita dall apparecchio Non é consentito l uso di adattatori prese multiple e o prolun ghe per l alimentazione generale dell apparecchio alla rete elet trica Prevedere un interruttore onnipolare con distanza d apertura dei contatti uguale o superiore a 3 mm per l allacciamento alla rete elettrica come previsto dalle normative di sicurezza vigenti condizion...

Page 8: ...A PRESSIONE SONORA dBA 94 4 POTENZA SONORA dBA 103 8 PESO CON IMBALLO kg 704 Potere calorifico inferiore alle condizioni di riferimento 15 C 1013 hPa mbar Gas metano Hi 9 45 kWh Stm 34 02 MJ Stm Assorbimento totale in fase di partenza con trasformatore d accensione inserito La pressione sonora e stata rilevata con bruciatore funzionante alla portata termica nominale massima alle condizioni ambient...

Page 9: ...sosi 9 Viscosità combustibili liquidi 10 Potenza motore ventilatore 11 Tensione di alimentazione 12 Grado di protezione 13 Paese di costruzione e numeri di certificato di omologazione 14 Anno di costruzione 15 16 Codice a barre matricola bruciatore DATI REGISTRAZIONE PRIMA ACCENSIONE Modello Data ora Tipo di gas Indice di Wobbe inferiore Potere calorifico inferiore Portata gas Stm3 h Portata min g...

Page 10: ...identificazione bruciatore 1 3 2 10 4 6 9 11 7 15 13 8 5 5 14 12 0002938900_img_nom CAMPO DI LAVORO 2 3 4 5 6 7 kWx1000 5 10 mbar 15 20 0002923050 25 0 1 8 9 10 11 12 30 13 14 15 16 TBG 1600 MC TBG 1600 ME IMPORTANTE I campi di lavoro sono ottenuti su caldaie di prova rispondenti alla norma EN676 e sono orientativi per gli accoppiamenti brucia tore caldaia Per il corretto funzionamento del bruciat...

Page 11: ...O B2 ØE ØF ØM N L I B5 G C1 0002938900_dim C D A1 A2 A B1 B 45 4 5 R Modello A A1 A2 B B1 B2 B5 C C1 TBG 1600 MC 1460 695 765 1130 780 350 360 2290 234 Modello D E Ø F Ø G I LØ M N Ø TBG 1600 MC 735 545 503 DN100 685 630 M20 555 Modello R TBG 1600 MC 1455 ...

Page 12: ...ativa europea EN298 integrata con controllo tenuta valvole Quadro comandi comprendente interruttori marcia arresto au tomatico manuale selettore minimo massimo spie di funzio namento e di blocco Impianto elettrico con grado di protezione IP54 CARATTERISTICHE TECNICO FUNZIONALI Bruciatore di gas conforme alle normative europee EN 676 ed alle Direttive Europee 2006 42 CE 2006 95 CE 97 23 CE 2004 108...

Page 13: ... di combustione con brucia tore montato Per consentire l apertura massima e facilitare quindi le opera zioni di manutenzione si consiglia di disporre la cerniera sul lato opposto rispetto alla posizione in cui è installata la rampa gas Per movimentare il corpo ventilante utilizzare le apposite cate ne o funi 32 da agganciare ai golfari Per una corretta installazione del corpo ventilante seguire la...

Page 14: ... 8 alla leva della farfalla di regolazione della portata gas 26 IMPORTANTE Prima di chiudere il bruciatore collegare i cavi di accen sione e ionizzazione ai terminali degli elettrodi quindi bloc care gli stessi al raccordo mandata gas tramite fascetta 26 8 0002938910B ...

Page 15: ...ubazione orizzontale dopo il filtro Il regolatore di pressione del gas deve essere regolato mentre lavora alla massima portata effettivamente utilizzata dal brucia tore La pressione in uscita deve essere regolata ad un valore leg germente inferiore a quella massima realizzabile quella che si ottiene avvitando quasi a fine corsa la vite di regolazione nel caso specifico avvitando la vite di regolaz...

Page 16: ... devono essere adatti a sopportare la corrente massima assorbita dal bruciatore Prevedere un interruttore onnipolare con distanza d apertura dei contatti uguale o superiore a 3 mm per l allacciamento alla rete elettrica come previsto dalle normative di sicurezza vigenti Per i collegamenti elettrici linea e termostati vedere il relativo schema elettrico Sguainare l isolante esterno del cavo di alim...

Page 17: ...entilazione la farfalla gas e la serranda aria vengono portate nella posizione di accensione quindi si inse risce il trasformatore d accensione e si aprono le valvole del gas La presenza della fiamma rilevata dal dispositivo di controllo consente il proseguimento e il completamento della fase di ac censione con la disinserzione del trasformatore Successivamente si verifica il passaggio al secondo ...

Page 18: ...lazione aria in senso inverso a quello precedente La rotazione all indietro e quindi la riduzione dell erogazione aria e gas avviene a brevi intervalli di tempo Con questa manovra il sistema di modulazione cerca di equi librare la quantità di calore fornito alla caldaia con quello che la stessa cede all utilizzo La sonda di modulazione applicata alla caldaia rileva le variazioni di richiesta ed au...

Page 19: ... sulla vite viti 12 in corrispondenza della leva di azionamento della serranda aria 34 12 34 33 0002938910A Inserire ora l interruttore 1 l apparecchiatura di comando riceve così tensione ed il programmatore determina l inserzione del bruciatore come descritto nel capitolo Descrizione del fun zionamento Durante la fase di preventilazione accertarsi che il pressostato di controllo della pressione a...

Page 20: ...nza del servomotore Verificare con gli appositi strumenti i parametri di combustione in primo stadio CO2 max 10 O2 min 3 CO max 0 1 Correggere se necessario l erogazione di aria comburente e gas agendo sulle viti 12 e 33 del modulatore REGOLAZIONE DELLA PORTATA DI ACCENSIONE Una volta effettuata la regolazione della potenza minima oc corre spegnere il bruciatore e verificare che l accensione avven...

Page 21: ...o rileva una pressione superiore a quella a cui è regolato Il pressostato di massima utilizza il contatto NC normalmente chiuso che si trova chiuso quando il pressostato rileva una pres sione inferiore a quella a cui è regolato La regolazione dei pressostati di minima e di massima deve quindi avvenire all atto del collaudo del bruciatore in funzione della pres sione che si riscontra di volta in vo...

Page 22: ...ella corrente di ionizzazione necessario a far funzionare l apparecchiatura è riportato nello schema elettrico Il bruciatore dà una corrente nettamente superiore tale da non richiedere normalmente alcun controllo Qualora comunque si voglia misurare la corrente di ionizzazione bisogna collegare un microamperometro in serie al cavo dell elet trodo di ionizzazione come rappresentato in figura PIN 2 X...

Page 23: ...abella dei colori qui sotto INDICAZIONI DI STATO OPERATIVE Durante l accensione si hanno indicazioni di stato secondo la seguente tabella Tabella codici colori per la spia LED Condizione Sequenza colori Colori Condizioni di attesa TW altri stati intermedi Nessuna luce Fase di accensione Giallo intermittente Funzionamento corretto intensità di corrente rilevatore fiamma supe riore al minimo ammesso...

Page 24: ...nto 3 Albero camme 4 Camme regolabili I Apertura massima aria 130 II Chiusura totale aria bruciatore fermo 0 III Apertura minima aria minore di camma IV 10 IV Apertura aria d accensione maggiore di camma III 30 PER MODIFICARE LA REGOLAZIONE DELLE CAMME UTIZ ZATE SI AGISCE SUI RISPETTIVI ANELLI I II III L IN DICE DELL ANELLO INDICA SULLA RISPETTIVA SCALA DI RIFERIMENTO L ANGOLO DI ROTAZIONE IMPOSTA...

Page 25: ...ta gas rispetto agli elettrodi per evitare che gli stessi si trovino a massa con conseguente bloccaggio del bru ciatore Occorrerà anche verificare che la scintilla dell elettrodo d accensione avvenga esclusivamente tra lo stesso ed il disco in lamiera forata vedi schema di regolazione testa di combus tione e distanza disco elettrodi per la versione senza pilota Effettuare l analisi dei gas di scar...

Page 26: ...24 34 0006160218_201704 PERICOLO ATTENZIONE Al momento della chiusura del bruciatore dopo aver colle gato i cavi degli elettrodi ai terminali bloccare gli stessi al raccordo mandata gas utilizzando una fascetta ...

Page 27: ...SA E CONDOTTI PRESSIONE ARIA PULIZIA ANNO COMPONENTI DI SICUREZZA GAS PRESSOSTATO GAS VERIFICA FUNZIONALE ANNO COMPONENTI VARI GAS MOTORI ELETTRICI CUSCINETTI VEN TOLA RAFFREDDAMENTO PULIZIA vedere se esistono indicazioni del fornitore ANNO LEVE TIRANTI SNODI SFERICI GIOCHI LUBRIFICAZIONE CONTROLLO EVENTUALI GIOCHI ANNO FILTRO DI LINEA PULIZIA SOSTITUZIONE CARTUCCIA RICAMBIO ANNO PARAMETRI DI COMB...

Page 28: ...l gas non è stata adeguatamente sfogata dall aria caso di prima accensione 3 La pressione del gas è insufficiente o eccessiva 4 Passaggio aria tra disco e testa troppo chiuso RIMEDIO 1 Invertire l alimentazione lato 230V del trasformatore di accensione e verificare con micro amperometro analogico 2 Sostituire il sensore fiamma 3 Correggere la posizione del sensore di fiamma e successivamente verif...

Page 29: ...ITALIANO 27 34 0006160218_201704 SCHEMI ELETTRICI ...

Page 30: ...ITALIANO 28 34 0006160218_201704 ...

Page 31: ...ITALIANO 29 34 0006160218_201704 ...

Page 32: ...E CONTATTORE ESTERNO KL CONTATTORE DI LINEA KD CONTATTORE TRIANGOLO KY CONTATTORE DI STELLA KT TEMPORIZZATORE MV MOTORE VENTOLA N1 REGOLATORE ELETTRONICO PA PRESSOSTATO ARIA Pm PRESSOSTATO DI MINIMA PM PRESSOSTATO DI MASSIMA S1 INTERRUTTORE MARCIAARRESTO S2 PULSANTE SBLOCCO S4 SELETTORE AUT MAN S5 COMMUTATORE MIN O MAX SG INTERRUTTORE GENERALE T2 TERMOSTATO 2 STADIO TA TRASFORMATORE D ACCENSIONE T...

Page 33: ...ITALIANO 31 34 0006160218_201704 SCHEMI ELETTRICI ...

Page 34: ...ITALIANO 32 34 0006160218_201704 ...

Page 35: ...ITALIANO 33 34 0006160218_201704 ...

Page 36: ...TRIANGOLO KY CONTATTORE DI STELLA KT TEMPORIZZATORE MV MOTORE VENTOLA N1 REGOLATORE ELETTRONICO PA PRESSOSTATO ARIA Pm PRESSOSTATO DI MINIMA P M PRESSOSTATO DI MASSIMA PmP PRESSOSTATO DI MINIMA RAMPA PILOTA S1 INTERRUTTORE MARCIAARRESTO S2 PULSANTE SBLOCCO S4 SELETTORE AUT MAN S5 COMMUTATORE MIN O MAX SG INTERRUTTORE GENERALE T2 TERMOSTATO 2 STADIO TA TRASFORMATORE D ACCENSIONE TC TERMOSTATO CALDA...

Page 37: ...agram 13 Gas supply line 13 Electrical connections 14 Operating description 15 Modulation operation description 16 Starting up and regulation 17 Ionisation current measurement 20 Diagram for regulation of combustion head and electrode disk distance 20 Control box for LME73 gas burners 21 Detail of the modulation control motor SQM 53 for cam adjustment 22 Air regulation on the combustion head 23 Ma...

Page 38: ...omist PYR RiNOx Spark Sparkgas TBG TBL TS IBR IB Variant LX for low NOx emissions respect the minimal regulation of the European Directives 2009 142 CE D A G 2004 108 CE C E M 2006 95 CE D B T 2006 42 CE D M and compliant with the European Standards prEN 676 2012 gas and dual fuel gas side prEN 267 2012 diesel and dual fuel diesel side EN 60335 1 2012 01 EC 2014 01 all burners Cento 12 Genuary 201...

Page 39: ...ature between 10 C and 40 C The storage time is 3 years GENERAL INSTRUCTIONS The equipment production date month year is written on the burner identification plate located on the equipment The device is not suitable to be used by persons including children with reduced physical sensory or mental capacities or lack of experience or knowledge such persons can use the device only if they can benefit ...

Page 40: ...d remove the control wheels from their position Render harmless any potentially dangerous parts INSTRUCTIONS FOR START UP INSPECTION USE AND MAINTENANCE Start up inspection and maintenance of the equipment must only be carried out by qualified technicians in compliance with current regulations Once you have fastened the burner to the power generator make sure that during testing the flame produced...

Page 41: ...r the power absorbed by the equipment The use of adaptors multiple plugs and or extension leads to supply power from the mains to the appliance is not allowed For the connection to the mains fit an omnipolar switch with a contact opening gap equal to or greater than 3 mm in accor dance with current safety regulations Overvoltage category III Use only double insulated cables with external thickness...

Page 42: ...ION MECHANICAL CAM SOUND PRESSURE dBA 94 4 SOUND POWER dBA 103 8 WEIGHT WITH PACKING kg 704 Calorific power lower than reference conditions 15 C 1013 hPa mbar Natural gas Hi 9 45 kWh Stm 34 02 MJ Stm Total absorption at start with ignition transformer on The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer s laboratory environment conditio...

Page 43: ...iquid fuel viscosity 10 Fan motor power 11 Power supply voltage 12 Protection rating 13 Country of manufacture and homologation certificate num bers 14 Year of manufacture 15 16 Burner serial number bar code FIRST START UP RECORDING DATA Model Date Now Type of gas Lower Wobbe number Lower calorific power Gas flow Stm3 h Min gas flow rate Stm h Max gas flow rate Stm h Min gas power kW Max gas power...

Page 44: ...rner identification plate 1 3 2 10 4 6 9 11 7 15 13 8 5 5 14 12 0002938900_img_nom OPERATING RANGE 2 3 4 5 6 7 kWx1000 5 10 mbar 15 20 0002923050 25 0 1 8 9 10 11 12 30 13 14 15 16 TBG 1600 MC TBG 1600 ME IMPORTANT The operating ranges are obtained from test boilers corresponding to Standard EN676 and are indicative of the burner boiler com bination For correct working of the burner the size of th...

Page 45: ...S B2 ØE ØF ØM N L I B5 G C1 0002938900_dim C D A1 A2 A B1 B 45 4 5 R Model A A1 A2 B B1 B2 B5 C C1 TBG 1600 MC 1460 695 765 1130 780 350 360 2290 234 Model D E Ø F Ø G I LØ M N Ø TBG 1600 MC 735 545 503 DN100 685 630 M20 555 Model R TBG 1600 MC 1455 ...

Page 46: ...alve seal control Control panel including on off automatic manual operation switches and minimum maximum selector operation and lock our indicator lights Electric system with protection class IP54 TECHNICAL FUNCTIONAL CHARACTERISTICS Gas burner compliant with European Standards EN 676 and European Directives 006 42 EC 2006 95 EC 97 23 EC 2004 108 EC Operation at two progressive stages modulating C...

Page 47: ...combustion head with fitted burner To enable the maximum opening and so facilitate maintenance operations it is recommended to install the hinge opposite to the position where the gas train is installed To move the ventilating body use the appropriate chains or ropes 32 and hook them to the eyebolts For a correct installation of the ventilating body follow the proce dure described below Position t...

Page 48: ... joint 8 to the lever of the gas flow rate regulation throttle valve 26 IMPORTANT Before lighting the burner connect the ignition and ionisa tion leads to the electrodes terminals Then secure them to the gas delivery fitting using a clamp 26 8 0002938910B ...

Page 49: ...pipe after the filter The gas pressure regulator must be adjusted when it is working at the maximum output actually used by the burner The outgoing pressure must be adjusted to a value slight ly below the maximum possible value the value obtained by screwing in the adjustment screw almost completely in this case the outgoing regulator pressure increases as the adjust ment screw is tightened and de...

Page 50: ...t be suitable to support the maximum current ab sorbed by the burner The mains supply connection requires an omnipolar switch with a contact opening gap equal to or greater than 3 mm in accor dance with current safety regulations Refer to the wiring diagram for electrical connections line and thermostats Unsheathe the external insulating cover of the power cable to the necessary extent for the con...

Page 51: ...le and the air shutter are returned to the ignition position then the ignition transformer turns on and the gas valves open The presence of the flame detected by the control device per mits continuation and completion of ignition turning off the ignition transformer Then passing on to the second stage of power through the pro gressive opening of the gas throttle and the air gate at the same time A...

Page 52: ...otor The inverse rotation and therefore the air and gas supply reduc tion occurs shortly thereafter With this procedure the modulation system attempts to balance the amount of heat supplied to the boiler with respect to the amount the boiler releases for use The modulation probe installed on the boiler measures any varia tion requests and automatically adjusts fuel and combustion air supply by sta...

Page 53: ... fully Correct the air flow rate using screw s 12 by the air shutter control lever 34 12 34 33 0002938910A Now turn the switch null on This powers on the control device and the programmer turns on the burner as described in the chapter Operation description During pre ventilation make sure that the air pressure control switch changes its status If the air pressure switch does not detect sufficient...

Page 54: ...ombustion parameters in the 1st stage with ap propriate instruments C02 max 10 O2 min 3 CO max 0 1 If needed correct the combustion air and gas output using screws 12 and 33 of the modulator ADJUSTING THE FLOW RATE FOR IGNITION Once regulation of the minimum output has been carried out the burner needs to be switched off and check that ignition occurs properly If necessary it is possible to optimi...

Page 55: ...the NC normally closed contact which is closed when the pressure switch detects a pressure lower than its own setting Adjustment of minimum and maximum pressure values on the pressure switches must be performed when testing the burner on the basis of the pressure measured in each case The triggering opening of the circuit of any of the pressure swit ches when the burner is running flame on causes ...

Page 56: ...aximum ionisation current value required for a correct ope ration of the equipment is indicated in the wiring diagram The burner provides a significantly higher current and therefore does not normally require any checks at all Should however the ionisation current need to be measured a microammeter must be connected in series to the ionisation elec trode lead by opening the connector as illustrate...

Page 57: ... colour table below OPERATING STATUS INDICATIONS During ignition there are the following status indications as per the table below Colour code table for the indicator light LED Condition Colour sequence Colours Waiting conditions TW other intermediate statuses No light Ignition phase Intermittent yellow Correct operation current strength of flame detector above the mini mum allowed Green Incorrect...

Page 58: ...ference scale 3 Camshaft 4 Adjustable camshaft I Maximum air opening 130 II Total air closure burner stopped 0 III Minimum air opening lower than cam IV 10 IV Ignition air opening greater than cam III 30 TO MODIFY THE SETTING OF THE CAM USED USE THE RESPECTIVE RINGS I II III THE SCALE ON THE RING INDICATES THE ROTATION ANGLE SET FOR EACH CAM ON THE RESPECTIVE REFERENCE SCALE ...

Page 59: ...ser with respect to the electrodes making sure that they are not earthed which would result in the locking of the burner Verify also that the ignition electrode spark takes place exclusively between itself and the perforated sheet metal disk see combustion head and elec trode disk distance regulation diagram for the version without pilot Analyse combustion gases and check emissions values If it is...

Page 60: ...ENGLISH 24 34 0006160218_201701 DANGER CAUTION When turning on the burner after connecting the electrode leads to the terminals secure them to the gas delivery fitting using a clamp ...

Page 61: ...NING YEAR AIR PRESSURE PIPES AND OUTLET CLEANING YEAR SAFETY COMPONENTS GAS GAS PRESSURE SWITCH OPERATIONAL TEST YEAR VARIOUS COMPONENTS GAS ELECTRIC MOTORS BEARINGS COO LING FAN CLEANING see if the supplier s indications were provided YEAR LEVERS STRAP SYSTEM BALL JOINTS BACKLASH LUBRICATION CHECK FOR POSSIBLE BACKLASH YEAR LINE FILTER CLEANING REPLACEMENT SPARE CARTRIDGE YEAR COMBUSTION PARAMETE...

Page 62: ...rst igni tion 3 The gas pressure is insufficient or excessive 4 Air flow between disc and head too narrow REMEDY 1 Invert the ignition transformer power supply 230V side and check using an analogue micro ammeter 2 Replace flame sensor 3 Correct the position of the flame sensor and then check for its efficiency by connecting the analogue micro amme ter 4 Check visually and using the instrument 5 Re...

Page 63: ...ENGLISH 27 34 0006160218_201701 WIRING DIAGRAMS ...

Page 64: ...ENGLISH 28 34 0006160218_201701 ...

Page 65: ...ENGLISH 29 34 0006160218_201701 ...

Page 66: ...RANSFORMER OPERATION INDICATOR LIGHT KE EXTERNAL CONTACTOR KL LINE CONTACTOR KD TRIANGLE CONTACTOR KY STAR CONTACTOR KT TIMER MV FAN MOTOR N1 ELECTRONIC REGULATOR PA AIR PRESSURE SWITCH Pm MINIMUM PRESSURE SWITCH PM MAXIMUM PRESSURE SWITCH S1 START STOP SWITCH S2 RELEASE BUTTON S4 AUT MAN SELECTOR S5 MIN O MAX SWITCH SG MAIN SWITCH T2 2ND STAGE THERMOSTAT TA IGNITION TRANSFORMER TC BOILER THERMOST...

Page 67: ...ENGLISH 31 34 0006160218_201701 WIRING DIAGRAMS ...

Page 68: ...ENGLISH 32 34 0006160218_201701 ...

Page 69: ...ENGLISH 33 34 0006160218_201701 ...

Page 70: ...CTOR KL LINE CONTACTOR KD TRIANGLE CONTACTOR KY STAR CONTACTOR KT TIMER MV FAN MOTOR N1 ELECTRONIC REGULATOR PA AIR PRESSURE SWITCH Pm MINIMUM PRESSURE SWITCH P M MAXIMUM PRESSURE SWITCH PmP PILOT TRAIN MINIMUM PRESSURE SWITCH S1 START STOP SWITCH S2 RELEASE BUTTON S4 AUT MAN SELECTOR S5 MIN O MAX SWITCH SG MAIN SWITCH T2 2ND STAGE THERMOSTAT TA IGNITION TRANSFORMER TC BOILER THERMOSTAT TS SAFETY ...

Page 71: ......

Page 72: ...t Il presente catalogo riveste carattere puramente indicativo La casa pertanto si riserva ogni possibilità di modifica dei dati tecnici e di quant altro in esso riportato Information contained in this catalogue is not binding The manufacturer reserves the right to change the technical data and any other data it contains ...

Reviews: