Limitorque Master Station III FCD LMENIM5001-02 – 12/13
54
Table 8.11 - Function Code -16 Message Breakdown
Query
Response
01
MSIII Unit Address
01
MSIII Unit Address
10
Function
10
Function
13
Starting Address Hi
13
Starting Address Hi (Register 45050; MOV50)
B9
1
Starting Address Lo
B9
Starting Address Lo (Register 45050; MOV50)
00
Number of Registers Hi
00
Number of Registers Hi
03
Number of Registers Lo
03
Number of Registers Lo
06
Byte Count
5569
Error Check (CRC)
03
Preset Data Hi (MOV 50)
00
2
Preset Data Lo (MOV 50)
03
Preset Data Hi (MOV 51)
00
Preset Data Lo (MOV 51)
03
Preset Data Hi (MOV 52)
00
Preset Data Lo (MOV 52)
6ABB
Error Check (CRC)
NOTE 1:
13B9h equals register address 45050 (field unit 50 command register)
NOTE 2:
0300h requests the register to be preset with 768d (Field unit close)
See Tables 8.12 and 8.13 for valid register operations. For further reference, see DDC (Modbus) Field
Unit Installation and Maintenance manual LMENIM2329.
Table 8.12 - Valid Command Register Operations
Host Commands to Field Unit Register 1
Value (Decimal)
Function
Null Command
0
No action
Open
256
Open actuator
Stop
512
Stop actuator
Close
768
Close actuator
Reset Field Unit
1024
Reset processor
Start Network ESD
1280
ESD initiate
Stop Network ESD
1536
ESD terminate
Engage Relay #1
2304
S1 or R1 (opt)
Engage Relay #2
2560
S2 or R2 (opt)
Engage Relay #3
2816
R3 (opt)
Engage Relay #4
3072
R4 (opt)
Engage Relay #5
3328
R5 (opt)
Engage Relay #6
3584
R6 (opt)
Engage Relay #7
3840
R7 (opt)
Disengage Relay #1
4352
S1 or R1 (opt)
Disengage Relay #2
4608
S2 or R2 (opt)
Disengage Relay #3
4864
R3 (opt)
Disengage Relay #4
5120
R4 (opt)
Disengage Relay #5
5376
R5 (opt)
Disengage Relay #6
5632
R6 (opt)
Disengage Relay #7
5888
R7 (opt)
Move-To (Enable)
1
6656
Initiates “move-to”
Engage Relay #8
6912
R8 (opt)
Disengage Relay #8
7168
R8 (opt)
Note 1: This is a two-step command. A valid value must be written to Register 2 before issuing this command.