47
Limitorque Master Station III FCD LMENIM5001-02 – 12/13
flowserve.com
Table 8.4 - Register Definitions (continued)
Register #
Description
Meaning
10
Fault Register
16 Bits of field status
Bit 0 Open inhibit active
Bit 1 Close inhibit active
Bit 2 Not Used
Bit 3 Not Used
Bit 4 One or more phases are missing
Bit 5 Reverse phase sequence is occurring
Bit 6 ESD conflict
Bit 7 Inhibit conflict
Bit 8 CSE in local/stop (input must be set for CSE and enabled)
Bit 9 Not Used
Bit 10 Network emergency shutdown is active
Bit 11 Local PB emergency shutdown is active
Bit 12 Field unit microprocessor has reset since the last poll
Bit 13 MX in stop mode
Bit 14 Opening in local mode
Bit 15 Closing in local mode
11
Digital Outputs
Value of 16 Digital Outputs
Bit 0 Close contactor (Interlocked)
Bit 1 Open contactor (Interlocked)
Bit 2 S1 or R1 (Opt)
Bit 3 S2 or R2 (Opt)
Bit 4 R3 (Opt)
Bit 5 R4 (Opt)
Bit 6 R5 (Opt)
Bit 7 R6 (Opt)
Bit 8 R7 (Opt)
Bit 9 Network Relay
Bit 10 R8 (Opt)
Bit 11 Not Used
BIT 12-15 MOV Series (MX = 1, MXa = 9, QX = 6, UEC-3 = 0, UEX = 10)
12
Digital Inputs 1
Value of 16 Digital Inputs
Bit 0 Remote Switch
Bit 1 Thermal Overload
Bit 2 Open Torque Switch
Bit 3 Open Limit Switch
Bit 4 Close Torque Switch
Bit 5 Close Limit Switch
Bit 6 Not Used
Bit 7 Not Used
Bit 8 User Input 0 (Default=ESD), Terminal 30
Bit 9 User Input 1 (Default=Open Inhibit), Terminal 34
Bit 10 User Input 2 (Default=Close Inhibit), Terminal 35
Bit 11 Remote Stop Input, Terminal 26
Bit 12 Remote Open Input, Terminal 25
Bit 13 Remote Close Input, Terminal 27
Bits 14-15 Not Used