Supplement to User Manual - ENGLISH
53
4
Modbus Register Addresses of Selected Physical Quantities
The following table is intended to provide assistance to the user.
It contains a number of selected Modbus register addresses of the most commonly used physical quantities and diagnos-
tic values. The measured values are scaled.
The Modbus register addresses are 0-based. If the transmitter is connected to a 1-based control system or software, the
Modbus register address in the following table has to be increased by 1.
Tab. 4.1: Modbus register addresses
address
measuring
channel A
address
measuring
channel B
address
calculation
channel Y ¹
address
calculation
channel Z ¹
preset
unit of
measure-
ment ²
remarks
physical quantity
medium temperature T
fluid
(at
the location where the flow rate
is measured, supply line or re-
turn line)
1004
2004
-
-
°C
medium temperature T
aux
(the
other temperature, return line
or supply line)
1020
2020
-
-
medium pressure p
fluid
(at the
location where the flow rate is
measured, supply line or return
line)
1036
2036
-
-
bar
medium pressure p
aux
(the
other pressure, return line or
supply line)
1052
2052
-
-
signal amplitude
1068
2068
-
-
-
sound speed
1084
2084
10084
9084
m/s
flow velocity
1100
2100
10100
9100
volumetric flow rate
1116
2116
10116
9116
m³/h
volumetric flow rate,
totalizer for positive flow direc-
tion
1132
2132
10132
9132
m³
volumetric flow rate,
totalizer for negative flow direc-
tion
1148
2148
10148
9148
standard volumetric flow rate
(gas measurement)
1164
2164
10164
9164
m³/h
standard volumetric flow rate,
totalizer for positive flow direc-
tion
1180
2180
10180
9180
m³
standard volumetric flow rate,
totalizer for negative flow direc-
tion
1196
2196
10196
9196
mass flow rate
1212
2212
10212
9212
kg/s
¹
For information regarding calculation channel Y, Z see user manual FLUXUS or PIOX.
² The preset unit of measurement can be changed. For an overview of the IDs of the unit of measurement see annex A.
Summary of Contents for FLUXUS ADM 5 07 Series
Page 4: ...Modbus Server Supplement to User Manual 4 SU_ModbusV2 8 2015 03 02...
Page 6: ...Modbus Server Erg nzung zur Bedienungsanleitung DEUTSCH 6 SU_ModbusV2 8 2015 03 02...
Page 46: ...Modbus Server Erg nzung zur Bedienungsanleitung DEUTSCH 46 SU_ModbusV2 8 2015 03 02...
Page 48: ...Modbus Server Supplement to User Manual ENGLISH 48 SU_ModbusV2 8 2015 03 02...