Supplement to User Manual - ENGLISH
57
6
Request of a Physical Quantity or a Diagnostic Value
Every physical quantity or every diagnostic value is provided in a block of 16 Modbus registers in predefined Modbus reg-
ister address ranges.
Besides the unscaled and scaled measured values, the state of the measured value and the unit of measurement, among
others, can be requested as parameters (see Tab. 6.3).
The Modbus register address results as a sum of:
• the start address,
• the offset of the physical quantity or diagnostic value and
• the offset of the parameter.
Start Address
Each channel is assigned to a start address:
For the start address for channel-independent diagnostic values see section 8.1.
Offset of the Physical Quantity or Diagnostic Value
For the calculation of the Modbus register address, an offset is added to the start address of the channel.
Tab. 6.1: Start addresses of the channels
channel
start address
A
1000
B
2000
C
3000
D
4000
Z
9000
Y
10000
Tab. 6.2: Offset for the physical quantities or the diagnostic values
value
offset
preset unit of
measurement
note
calculation
possible
1
physical quantity
medium temperature T
fluid
(at the location
where the flow rate is measured, supply line or
return line)
0
°C
no
medium temperature T
aux
(the other tempera-
ture, return line or supply line)
16
medium pressure p
fluid
(at the location where
the flow rate is measured, supply line or return
line)
32
bar
medium pressure p
aux
(the other pressure,
return line or supply line)
48
signal amplitude
64
-
sound speed
80
m/s
yes
flow velocity
96
m/s
volumetric flow rate
112
m³/h
volumetric flow rate,
totalizer for positive flow direction
128
m³
volumetric flow rate,
totalizer for negative flow direction
144
standard volumetric flow rate
(gas measurement)
160
m³/h
Summary of Contents for FLUXUS ADM 5 07 Series
Page 4: ...Modbus Server Supplement to User Manual 4 SU_ModbusV2 8 2015 03 02...
Page 6: ...Modbus Server Erg nzung zur Bedienungsanleitung DEUTSCH 6 SU_ModbusV2 8 2015 03 02...
Page 46: ...Modbus Server Erg nzung zur Bedienungsanleitung DEUTSCH 46 SU_ModbusV2 8 2015 03 02...
Page 48: ...Modbus Server Supplement to User Manual ENGLISH 48 SU_ModbusV2 8 2015 03 02...