Supplement to User Manual - ENGLISH
75
11.3
Request of the Totalizer for the last 24 h (Request in Intervals)
The values of the totalizers for the last 24 h can be requested for the following physical quantities:
• volumetric flow rate
• standard volumetric flow rate
• mass flow rate
• heat flow rate
The values of the totalizers are stored once per day according to the trigger time set for the last three days (shift register).
Trigger time (default): 0:00 am
Different trigger times can be defined (see Tab. 11.3).
For the Modbus register addresses of the values of the totalizers see Tab. 11.4.
Tab. 11.2: Reset of the totalizers to zero
Modbus register address
explanation
character
hexadecimal
100
channel ID
measuring channels
A...D
0x41...0x44
calculation channels
Z...Y
0x5A...0x59
all channels
*
0x2A
101
totalizer ID
positive totalizer
+
0x2B
negative totalizer
-
0x2D
both totalizers
*
0x2A
220
reset
0x01
Tab. 11.3: Defining the trigger time
value
data format
Modbus register address
trigger time
integer 32 bit
1st byte (lsb): second
2nd byte: minute
3rd byte: hour
4th byte: not used
23000 ...23001
Example:
Defining the trigger time on February 16th, 2014
Trigger time: 2:15 pm
Every day at 2:15 pm the current values of the totalizers for the last 24 h are stored.
On February 20th, 2014 after 2:15 pm, the values of the totalizer of the following days can be
requested:
1st day: (February 19th, 2:15 pm to February 20th, 2014, 2:15 pm)
2nd day: (February 18th, 2:15 pm to February 19th, 2014, 2:15 pm)
3rd day: (February 17th, 2:15 pm to February 18th, 2014, 2:15 pm)
Summary of Contents for FLUXUS ADM 5 07 Series
Page 4: ...Modbus Server Supplement to User Manual 4 SU_ModbusV2 8 2015 03 02...
Page 6: ...Modbus Server Erg nzung zur Bedienungsanleitung DEUTSCH 6 SU_ModbusV2 8 2015 03 02...
Page 46: ...Modbus Server Erg nzung zur Bedienungsanleitung DEUTSCH 46 SU_ModbusV2 8 2015 03 02...
Page 48: ...Modbus Server Supplement to User Manual ENGLISH 48 SU_ModbusV2 8 2015 03 02...