M-K Compressor Expansion Automat
Installation and operating instructions
Appendix 2; Technical data, specifi cations, electrical equipment.
Flexcon control unit, M-K/S, operating mode menu.
Display 21
Entry, indicate **1** for version
with two units ** (Master-
Slave) per unit. See also
page 5, Operating modes.
Display 22
Carry out at place of setup
before fi rst start
(cap valve system connection
and valve fi lling “OFF”).
Display 23
Information on ensuring, that
the basic vessel is aligned
and free of additional loads
or reliefs.
Display 24
Entry of the actual-mass
available at the level sensor
of the basic vessel.
Display 25
Set when limits are exceeded
as a result of unpermitted
load or relief on the basic
vessel.
The required starting
condition is to be created and
the procedure repeated from
display (13) 22.
Control.)* Service programming mode. )* removed
This programming enables the trained service engineers to modify further
control parameters. Important presets, which are programmed at the factory,
are shown below.
Option Leak probe **, standard
: **2** not available (see display 3: “ – “).
Option Leak probe **, as ordered
: **1** available (see display 3: “ * “).
Option Backup (2 units **), standard
: **2** not available (see display 3: “ – “).
Option Backup, as ordered
: **1** available (see display 3: “ * “).
)*
Backup 2 on 1, as ordered:
Second compressor unit **, parallel mode
: **2** not available.
Second compressor unit **, backup mode
: **1** available.
Language, as ordered or
: **1** (1: D; 2: GB; 3: F; 4: NL)
Factory zero setting of level sensor; vessel number : as ordered (PN3; 6; 10; vessel size)
Smoothing factor
: **3**
Hysteresis, compressor 1 (2**), Valve 1, PN3
: *0.1* (Valve 1.1; 1.2 ***)
Hysteresis, compressor 1 (2**), Valve 1, PN6; 10
: *0.2* (Valve 1.1; 1.2 ***)
Turn-on delay compr. 1 (2 **), Valve 1
: *03sec* (Valve 1.1; 1.2 ***)
Turn-off delay compr. 1 (2 **), Valve 1
: *01sec* (Valve 1.1; 1.2 ***)
Display 13;
system pressure, as ordered or
: *02.0* (default 2bar gas pre-pressure
standard PN3; 6; 10)
Display 14;
min. water level
: *05%*
Display 15;
max. water level
: *95%*
Display 16;
min. pressure PN3
: System pressure minus 0.3 bar.
Min. pressure PN6; 10
: System pressure minus 0.4 bar.
Display 17;
max. pressure PN3
: System pressure plus 0.3 bar.
Max. pressure PN6; 10
: System pressure plus 0.4 bar.
Display 18;
Filling level On
: *06%* (Falling level. On above 0%.)
Display 19;
Filling level Off
: *08%* (Rising level.)
Display 20;
change time
: *10 days*
Display 21;
Parallel mode (2 units **,
Master- Slave), Standard
: **2** not available (see display 3: “ – “).
Parallel mode, as ordered
: **1** available (see display 3: “ * “).
)*
)*
RS485 datacable required at site.
** Accessory, addition *** Special version
6ALUEEXCEEDSTOLERANCE
#ONTINUEWITH2%4
.OTPOSSIBLE
:EROSETTING
OPERATE
NEXT
:EROSETTING
OFLEVELSENSOR
%3#
2%4
2%4
%3#
:EROSETTING
.O
9ES0RESSKEY
6ESSELEMPTY
0RESSKEY
#ONFIRM
#ANCELWITH
,OAD
:EROSETTING
2%4
%3#
+G
"
0AGE
!
0AGE
%3#
2%4
2%4
%3#
%3#
2%4
NOTPROVIDED
PROVIDED
0ARALLELOPERATION
2%4
2%4
3AMPLEDISPLAYS
18502426 broch Flexcon M-K_UK.indd 22
18502426 broch Flexcon M-K_UK.indd 22
13-07-2006 08:55:51
13-07-2006 08:55:51