Air handling unit
Activation/changing of functions
The control unit in the eQ PRIME has powerful standard
software that allows functions to be activated, changed or
removed retroactively. This is done from the Configuration
menu. To access this menu, it is necessary to log in using
8888. Below is a list of the most common changes.
Note that a new sensor may be required after making
a change. Do not hesitate to contact FläktGroup support for
further information, advice or help regarding
settings. Tel. +46 36 193003.
It is usually necessary to restart the control unit in order
or the changes to be applied. This can be done with a
parameter at the bottom of each sub-menu.
Function
Search path (Parameter)
Comment
Weather compensation,
temperature
(Summer/Winter
compensation)
MAIN INDEX
Ú
CONFIGURATION
Ú
CONFIGURATION 2
Ú
SU/WI COMP TMP
For function description, see page 33.
Outdoor temperature
compensation fan setpoints
MAIN INDEX
Ú
CONFIGURATION
Ú
CONFIGURATION 2
Ú
FAN COMP OUTS TMP
.
For function description, see page 30.
Control mode fans
MAIN INDEX
Ú
CONFIGURATION
Ú
CONFIGURATION 1
Ú
FAN CONTROL MODE
Available choices for eQ PRIME:
Fixed speed (Fixed speed)
Flow (Flow control)
Pressure (Pressure control)
SupplySlv (Pressure control extract air,
flow control supply air)
ExhaustSlv (Pressure control supply air,
flow control extract air)
Control mode, temperature
MAIN INDEX
Ú
CONFIGURATION
Ú
CONFIGURATION 1
Ú
TMP CONTROL MODE
Available choices for eQ PRIME:
Supply air (Supply air control)
RmSplyC (cascade control, room)
ExhSplyC (Cascade control, extract air)
RmSplyC Su (Summer room control,
winter supply air control)
ExSplyC Su (Summer extract air control,
winter supply air control)
Room (Room temperature control)
Extract air (Extract air temperature control)
HOTC (Heat exchanger optimised temperature
control)
Night cooling
MAIN INDEX
Ú
CONFIGURATION
Ú
CONFIGURATION 2
Ú
NIGHT COOLING
For function description, see page 23.
Unoccupied mode
MAIN INDEX
Ú
CONFIGURATION
Ú
CONFIGURATION 2
Ú
TMP START
For function description, see page 24.
Boost
MAIN INDEX
Ú
CONFIGURATION
Ú
CONFIGURATION 2
Ú
BOOST
For function description, see page 25.