Minimum flows for duct-mounted electric heaters
1 Rectangular air heater (400x400) with a circular
connection for output variant 3 (15 kW)
2 Rectangular air heater (500x500) with circular connection,
all output variants.
Connection
Ø/WxH
Output, kW
Variant 1
Min. flow
m
3
/s
Ø315
3
0.12
Ø400
1
5
0.19 (0.24
1
)
Ø500
2
12
0.37
800x400
12
0.48
1100x500
17
0.82
1400x600
20
1.3
1400x800
30
1.7
Connection
Ø/WxH
Output, kW
Variant 2
Min. flow
m
3
/s
Ø315
5
0.12
Ø400
1
9
0.19 (0.24
1
)
Ø500
2
17
0.37
800x400
17
0.48
1100x500
30
0.82
1400x600
34
1.3
1400x800
48
1.7
Connection
Ø/WxH
Output, kW
Variant 3
Min. flow
m
3
/s
Ø315
9
0.12
Ø400
1
15
0.19 (0.24
1
)
Ø500
2
24
0.37
800x400
24
0.48
1100x500
43
0.82
1400x600
54
1.3
1400x800
75
1.7
Unit size
aaa
Min. flow
m
3
/s
005
0.27
008
0.50
011
0.7
018
1.1
023
1.6
032
1.9
041
2.4
050
3.2
Minimum flows for air handling unit-mounted electric
heaters