Alarm guide
Alarms
Alarm text
Cause
Action
Type
Fault handheld
terminal
Conn. Lost
The handheld terminal is
unable to communicate
with the control unit
• Disconnect and reconnect the cable from
the handheld terminal to the control unit
• If the fault persists, contact FläktGroup
tel.: +46 36 193003
–
Deviation alarm
humidity in
supply air
Sply hum deviation The measured humidity in
the supply air has deviated
from the setpoint for a
abnormally long time.
• Check the measured value using
the handheld terminal.
• If necessary, the alarm limit and alarm delay
can be adjusted using the handheld terminal.
B
Deviation alarm
humidity in the room
or in the extract
Room hum
deviation
The measured humidity in
the room or extract air has
deviated from the setpoint
for a abnormally long time.
• Check the measured value using
the handheld terminal.
• If necessary, the alarm limit and alarm delay
can be adjusted using the handheld terminal.
B
14