Air handling unit
Summer comp fan
From this menu, fan setpoints can be offset at high outdoor
temperatures.
MAIN INDEX
Ú
UNIT
Ú
FAN CONTROL
Ú
SUMMER COMP
If Delta is negative, the setpoints are lowered. If Delta is
positive, the setpoints are raised.
Summer comp fan
Outs air tmp start
Outs air tmp end
Delta
25.0 °C
30.0 °C
0.0%
Winter comp fan
From this menu, fan setpoints can be offset at low outdoor
temperatures.
MAIN INDEX
Ú
UNIT
Ú
FAN CONTROL
Ú
WINTER COMP
If Delta is negative, the setpoints are lowered. If Delta is
positive, the setpoints are raised.
Winter comp fan
Outs air tmp start
Outs air tmp end
Delta
5.0 °C
-20.0 °C
0.0%