Installation Instructions
9.12.14
Kapitel/Chapter 6: Installation Instructions - Seite/Page 111
CAUTION!
The AGT-generator is not allowed to be connected to an
inverter (without batteries)!
The Inverter generates voltage peaks, which can destroy the rectifier diodes of the generator!
A battery must always be connected to the inverter as a capacity!
Required cable cross-sections
The following recommended electrical cable dimensions (cross sections) are the minimum required sizes for a safe
installation.
All electrical safety installations have to be made on board.
Länge/length
1 - 3 m
4 - 6 m
7 - 10 m
11 - 15 m
16 - 20 m
16 mm²
70 A
63 A
55 A
48 A
42 A
25mm²
112 A
100 A
88 A
75 A
63 A
35mm²
155 A
140 A
125 A
110 A
95 A
50mm²
225 A
200 A
175 A
150 A
125 A
70mm²
315 A
285 A
250 A
220 A
190 A
95mm²
425 A
380 A
340 A
300 A
260 A
120mm²
540 A
490 A
440 A
400 A
360 A