MANUAL for the Stages Control Panel | CCE2.0
46
9.7. TIMER T06
(ex SW3 CD)
Enter the delay before complete emptying after the equipment has
been turned off.
The Timer
range
is from 0 h
to 24 h.
The factory set value is 1 h.
O h = Empties as soon as the equipment is switched off.
9.8. TIMER T07
(ex SW4 CD)
Enter the set-point time before partial emptying, by opening the
drain motor-valve, due to the conductivity being continuously
exceeded.
The Timer
range
is from 5 s
to 360 s.
The factory set value is 30 s.
9.9. TIMER
T08
Enter the maximum time for the filling to occur: Time for the
minimum level to be reached once the basin is on process of filling.
The Timer
range
is from 5 min
to 60 min.
The factory set value is 15 min.