MANUAL for the Stages Control Panel | CCE2.0
34
8.4. Conf. 0...10V or 4...20 mA:
Select what type of external analog signal the equipment will
receive:
❖
0…10 V
DC
❖
4…20 mA
8.5. UV lamp configuration
Switches the UV water treatment system on or off:
❖
Enabled (1)
❖
Disabled (0)
Note 1:
If the UV lamp is installed immersed in the basin, a bridge must be made in J18 (IN1)
Note 2:
Each time the UV lamp is switched on, an internal 12,000 hr operating counter is activated,
only when the equipment is running. After these 12,000 hours of operation, the A51 error is triggered
to replace the lamp.
Note 3:
After the lamp is replaced following an A51 error, the 12,000-hour counter must be reset by
switching the lamp off (0) and on (1) in this configuration menu.