MANUAL for the Stages Control Panel | CCE2.0
32
8.2.
Configuration Prior to Start-Up (Pre-Start-up)
The pre-start-up process can be enabled and the number of cycles to be repeated specified.
This process consists of carrying out the following repeat cycles for the number of times established:
Keep the water recirculation pump running for 10 minutes then empty the basin for 10 minutes.
This process cleans dust produced in the manufacturing process from the panel.
During the pre-start-up cycle, the duct fans for the air to be treated must be turned off. The UV lamp
must not be switched on during this process.
Once this function is enabled, the equipment must be started at the Manual mode (MAN) to proceed
with the start-up cycles.
The following control options are available:
❖
Enabled:
Enables the start-up process
❖
Disabled (*):
Enables the start-up process
❖
No. cycles :( min. 0 cycles /Max. 10 cycles)
Sets the start-up process cycles number.
The factory set value is 6 cycles
(*) Remember that you must disable this configuration if you
Want to start the equipment as standard mode.
Summary of Contents for CCE2.0
Page 2: ...MANUAL for the Stages Control Panel CCE2 0 2 ...
Page 14: ...MANUAL for the Stages Control Panel CCE2 0 14 Figure 3 4 Inside cover CCE2 0 standard ...
Page 53: ...MANUAL for the Stages Control Panel CCE2 0 53 13 Declaration of conformity 13 1 D C Machine ...
Page 54: ...MANUAL for the Stages Control Panel CCE2 0 54 13 2 D C Partly completed machinery ...
Page 55: ...MANUAL for the Stages Control Panel CCE2 0 55 14 Warranty ...
Page 56: ...MANUAL for the Stages Control Panel CCE2 0 56 ...
Page 57: ...IÓN F ...
Page 58: ...IÓN ...
Page 59: ...IÓN MAN P Ev1 Mv1 P P ...
Page 60: ...F IÓN ...
Page 61: ...IÓN ...
Page 62: ...IÓN MAN P Ev1 Mv1 P P ...