![fisair CCE2.0 Installation And Operation Manual Download Page 37](http://html1.mh-extra.com/html/fisair/cce2-0/cce2-0_installation-and-operation-manual_2294088037.webp)
MANUAL for the Stages Control Panel | CCE2.0
37
Read:
The following table shows the read function of each communication address:
Address
Description
Reading
2010
Status read On/Off
Off
→
0, On
→
1
2012
Read conductivity value
0-1999 µS/cm*
2014
Read temperature value ºC
Divide
the
result
by
100.
Ej. 1815
→
18,15ºC
2020
Read analogue input of signal 0-10 V
(Range 0-100)
Reading range 0-100. Divide the result by
10. Ej. 80
→
8 V
2022
Read analogue input of signal 4-20 mA
(Range 40-200)
Reading range 40-200. Divide the result by
10. Ej. 80
→
8 mA
Address
Description
Reading range
Factory setting
2030
Read Timer T01
30-1000s*
90s
2032
Read Timer T02
1-15 min *
5min
2034
Read Timer T03
1-60 min *
10min
2036
Read Timer T04
30-400min*
60min
2038
Read Timer T05
0-24h *
0min=never
2040
Read Timer T06
0-24h *
1h
2042
Read Timer T07
5-360s*
30s
2044
Read Timer T08
10-60min*
15min
*These values are shown in seconds
Address
Description
Reading
2116
Read equipment live J25
0
→
not live (yellow led [3]Off)
1
→
live (yellow led [3]On)
2118
Read general equipment failure J23
0
→
no equipment failure(red led [4] Off)
1
→
equipment failure(red led [4] On)
2120
Read general equipment operation
status J24
0
→
not working
1
→
in operation
2122
Read UV lamp operation status J10
0
→
Off (blue led [11] Off)
1
→
On (blue led [11] On)
2
→
Fault (blue led [11] flashing)
2124
Read filling solenoid valve status J13
0
→
Off (yellow led [12] Off)
1
→
On (yellow led [12] On)
2126
Read drainage motor valve power status
J14
0
→
No power (green led [13] Off)
1
→
Powered (green led [13] On)
2128
Read drain motor valve position J15
1
→
closed (green led [14] Off)
0
→
open (green led [14] On)
2130
Read Level position status
0
→
Low-minimum (Yellow led [15])
1
→
Operating level J17(Green led [15])
2
→
Maximum water level J16(red led [15])
3
→
Level fault (red led [15] flashing)
Summary of Contents for CCE2.0
Page 2: ...MANUAL for the Stages Control Panel CCE2 0 2 ...
Page 14: ...MANUAL for the Stages Control Panel CCE2 0 14 Figure 3 4 Inside cover CCE2 0 standard ...
Page 53: ...MANUAL for the Stages Control Panel CCE2 0 53 13 Declaration of conformity 13 1 D C Machine ...
Page 54: ...MANUAL for the Stages Control Panel CCE2 0 54 13 2 D C Partly completed machinery ...
Page 55: ...MANUAL for the Stages Control Panel CCE2 0 55 14 Warranty ...
Page 56: ...MANUAL for the Stages Control Panel CCE2 0 56 ...
Page 57: ...IÓN F ...
Page 58: ...IÓN ...
Page 59: ...IÓN MAN P Ev1 Mv1 P P ...
Page 60: ...F IÓN ...
Page 61: ...IÓN ...
Page 62: ...IÓN MAN P Ev1 Mv1 P P ...