12
9 Fault
listing
Fault
Number
Cause
Description
F01
F02
F03
F04
External Alarm
Fault 1
External Alarm
Fault 2
External Alarm
Fault 3
External Alarm
Fault 4
See Option parameters 19.1 to 19.4.
Subset : burner status.
F18
Not enough
setpoints entered
A fuel/air ratio profile has been selected which does not have at
least four setpoints commissioned.
x
Use commission ratio mode to enter more setpoints.
Subset : fuel code
F19
Circuit board
voltage reference
fault
The circuit board has an incorrect on-board reference level.
x
Ensure ALL analog inputs (4-20mA, 0 – 5v) are in the
range 0 to 5.0 volts. It is critical that none of the inputs
are higher than 5.0 volts.
x
If the problem persists even when all analog inputs are
disconnected, check EK37 and contact supplier.
Subset : +1 out of range, +2 zero check failed, +4 span check
failed.