Engineer’s key parameter list
No.
Name
Description
EK1
Low Voltage Digital Input 1 (PA5–PA11)
Shows the state of each input.
EK2
Low Voltage Digital Input 2 (PA6–PA11)
Where :
EK3
Low Voltage Digital Input 3 (PA7–PA11)
0 = OFF (Open circuit)
EK4
Low Voltage Digital Input 4 (PA8–PA11)
1 = ON
EK5
Low Voltage ‘HIGH’ input (PA9–PA11)
EK6
Low Voltage ‘AUTO input (P10–PA11)
EK11
Profile 1 Select – Line Voltage (PE9)
EK12
Profile 2 Select – Line Voltage (PE10)
EK13
Profile 3 Select – Line Voltage (PE11)
EK14
Profile 4 Select – Line Voltage (PE12)
EK16
Warming limit
0 - Measured value above warming limit, burner
free to modulate.
1 - Measured value below warming limit, burner
held at low fire if the control is in auto or
sequencing mode.
EK18
Boiler status
0 - Burner will not fire because the temperature /
pressure measured value has exceeded the high
control value.
1 - Burner will fire because the temperature /
pressure measured value has fallen below the
low control value.
EK19
Confirm to adjust
0 - Control not in commission mode or control is
in commission mode and drives moving to
setpoints.
1 - Control in commission mode and drives may
be adjusted using the UP/DOWN keys.
EK20
Drive moved
0 - Control not in commission mode or control is
in commission mode and drives have not been
moved using the UP/DOWN keys.
1 - Control in commission mode and drives have
been moved using the UP/DOWN keys.