Adjusting Cut IN and Cut OUT 

Follow steps 1 through 3 above. 

4.  If the display shows the angular positions of the servomotors, press the 

MODE

 key to change to 

option parameters.  Using the up or down key, move to 

OPTION 21.6 (22.6) for Cut In 

or

 21.7 

(22.7) for Cut Out.

  This is the control value the Nexus will start/stop the burner after reaching the 

cut in/out value.  This value is a differential value when option parameter 21.5 (22.5) is set at 2. 
That is, it is subtracted/added from/to the operating set point.  Once set, this value will follow any 
change in the set point programmed in option 21.1 (22.1). These values are actual values if 21.5 
(22.5) are set to 1. (see table below) 

Option parameter 

21.5 (22.5) value 

Meaning

0

No limits.

 The burner will run until another method is used to switch 

it off. 

1

Absolute limit.

  The values entered in option parameters 21.6 

(22.6) and 21.7 (22.7) are the actual limit values. 

2

Deviation limit. 

 The values entered in option parameters 21.6 

(22.6) and 21.7 (22.7) represent a deviation (i.e. offset) from the 
setpoint 1 control value.  This means that if the setpoint control 
value is changed, the limits are automatically changed 
correspondingly.

5.  Use the left or right arrow key to move the cursor to the lower portion of the display then - using 

the up/down arrow key, change the setting. 

6. Press 

the 

ENTER

 key to accept the new set point. 

7.  To exit and return to the normal run mode press the 

RUN

 key followed by the 

ENTER

 key.  See 

two examples below: 

Deviation Example: 

 

Opt  21.1 (22.1)* ...............set to............... 100 psi 

 

Opt  21.5 ...........................set to................... 2 

 

Opt  21.6 (22.6)* ...............set to................. 10 

 

Opt  21.7 (22.7)* ...............set to................. 10 

 Cut 

Out ..................................................... 110 

psi

 Set 

Point ................................................... 100 

psi

 

Cut In .......................................................... 90 psi 

New Set Point

  60 psi 

 

Cut Out ....................................................... 70 psi 

 

Set Point ..................................................... 60 psi 

 

Cut In .......................................................... 50 psi 

Summary of Contents for PPC6000 Series

Page 1: ...__________________________________2 3 Password _______________________________________________________2 4 Adjusting Cut IN and Cut OUT_____________________________________3 5 Manual Modulation _______...

Page 2: ...value and press the ENTER COM key 3 Password The only password an operator should require is the site Passcode This can be set as a number from 0 999 The factory default number is 154 The site Passcod...

Page 3: ...alue Meaning 0 No limits The burner will run until another method is used to switch it off 1 Absolute limit The values entered in option parameters 21 6 22 6 and 21 7 22 7 are the actual limit values...

Page 4: ...own on the display This function can be disabled via option parameter 1 1 To do so requires the suppliers highest passcode 6 Resetting the Control To reset the Nexus the MUTE RESET key will have to be...

Page 5: ...free to modulate 1 Measured value below warming limit burner held at low fire if the control is in auto or sequencing mode EK18 Boiler status 0 Burner will not fire because the temperature pressure me...

Page 6: ...essage since power up This should be zero unless there has been a problem EK26 Commission status Current commissioning mode where 0 Normal run mode 1 Adjust ratio mode 2 Commission ratio mode EK27 Com...

Page 7: ...nearest to the current modulation position EK37 Voltage reference error V The error between the measured voltage reference and the calibrated value 0 12 is the limit The displayed value shows volts NO...

Page 8: ...ut or trim not selected via serial comms 4 O2 setpoints or flow values incorrect 8 Option 30 6 not 0 16 Not modulating 32 In commission mode 64 Probe faulty see EK45 EK47 Oxygen setpoint Current oxyge...

Page 9: ...al Output 7 ON Daughterboard PZ15 PZ16 LOW VOLTAGE AND CURRENT ONLY 128 Digital Output 8 ON Daughterboard PZ17 PZ17 LOW VOLTAGE AND CURRENT ONLY EK61 Analog Input 1 Main Unit Terminal PB9 also boiler...

Page 10: ...task time The current longest internal software task time This is provided for manufacturers diagnostics only and may be removed in future versions EK76 Longest task number The current longest interna...

Page 11: ...xed by a letter This letter describes the status of the fault F This means that a fault e g PSU calibration fault has occurred and is still present The fault may be internal or external to the unit L...

Page 12: ...at least four setpoints commissioned x Use commission ratio mode to enter more setpoints Subset fuel code F19 Circuit board voltage reference fault The circuit board has an incorrect on board referen...

Page 13: ...than five degrees 3 During pre purge ignition or post purge when a drive moves from its setpoint 4 During modulation when a drive is not at its correct setpoint as defined by the commissioned fuel ai...

Page 14: ...to the control x This could be due to high levels of electrical interference getting into the product Check all cables are correctly screened and screens are terminated correctly Ensure the mains supp...

Page 15: ...5 and re commission or restore with option parameter 45 2 x This could be due to high levels of electrical interference getting into the product Check all cables are correctly screened and screens are...

Page 16: ...en level exceeded 15 0 during auto trim commissioning The burner is shutdown Subset Last auto trim commission setpoint 32 if adding air L58 Flue temperature low alarm value exceeded The measured flue...

Page 17: ...he engineer to ensure the new servo is mechanically fixed the same way as the original one Subset Invalid profile 100 101 to 104 3 The selected profile has been uploaded from a PC but has not been ver...

Page 18: ...st steam boilers When using only a proportional control the system rarely achieves set point as the burner firing rate is lowered as the pressure comes up At some point the input meets the actual dema...

Page 19: ...4 for set point 1 PID1 and 22 2 22 3 and 22 4 for set point 2 PID2 These values are adjustable using the Site Passcode 154 11 The Startup Shutdown Stages The startup shutdown stages are as follows Sta...

Page 20: ...The fuel and air motors are moved down until they are stopped by the closed position micro switches in the servos The final positions are compared with the closed positions stored in memory and must...

Page 21: ...fuel profile select input is removed PE9 10 11 or 12 the control will immediately move to status 1 10 Ignition The controller confirms all required drives are at their ignition positions and gives an...

Page 22: ...sing PA9 PA11 this control will move to status 17 If the AUTO input is removed by opening PA10 PA11 this control will modulate down to low fire then jump to status 15 Note Terminal PE7 will not be ene...

Page 23: ...23...

Page 24: ...ch is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES A...

Reviews: