7
No.
Name
Description
EK32
Number of commission setpoints
The number of setpoints entered in the current
commission ratio session :
0 - No setpoints entered.
1 - Close setpoint only.
2 - Close and purge setpoints.
3 - Close, purge and ignition.
4 - 24 - profile setpoints.
EK33
Modulation mode
The current modulation mode :
0 - Auto mode.
1 - Manual from external input.
2 - Manual from keyboard.
3 - Boiler sequencing control.
4 - Low fire hold.
EK36
Nearest setpoint
The number of the profile setpoint which is
nearest to the current modulation position.
EK37
Voltage reference error (V)
The error between the measured voltage
reference and the calibrated value.
0.12 is the limit. The displayed value shows volts
NOTE:
If value goes to 0.13, F19 will be
generated.
EK38
Boiler Sequencing Status
Currently unused.
EK39
Fuel Swap Status
Currently unused.
EK40 Shutdown
setpoint
The nearest setpoint (EK36) when the burner
last locked out.
EK42
Adjust ratio counter
The number of times adjust ratio mode has been
used.
EK43
Commission ratio counter
The number of times commission ratio mode has
been used.
EK44
Oxygen measured value
The current flue oxygen value as measured by
the FIREYE probe (if fitted).